High Performance Vector Control/Torque Control Inverter User Manual
Chapter 6 Parameter Description 67
6.2 Main and Auxiliary Reference Parameter (Group P1)
In process open loop control mode (P0.03=0 or P0.03=4), the main reference value f
m
will be added with
an auxiliary reference value f
a
, and it results in process open loop combination frequency reference f
com
.
Fig.6-3 Open loop main and auxiliary reference combination
The process open loop auxiliary reference mode P1.00 is selected as follows:
0: none; 1: AI1; 2: AI2; 3: AI3; 4: DI
Such calculations as “add”, “subtract”, “bias”, “max” and “min” are available for main reference value f
m
and auxiliary reference value f
a.
Through the setting of parameters in group P6, the frequency change range of the auxiliary reference
can be reduced to realize the fine tuning function.
The process open loop reference main and auxiliary relation calculation parameter P1.01 is defined as
follows:
0: Main reference + auxiliary reference: The auxiliary frequency reference value is superimposed on the
main reference, the function is “add”.
Fig.6-4 Process open loop main and auxiliary reference calculation 0
Open loop combination reference f
com
=main reference f
m
+auxiliary reference f
a
1: Main reference - auxiliary reference: The auxiliary frequency reference value is superimposed on the
main reference, the function is “subtract”.
P1.00 0~4(0)
P1.01
Open loop reference main and auxiliary relation
calculation
0~5(0)
Frequency
Time
Frequency
Time
Open loop auxiliary reference mode