Controller Application Software Upgrade Procedures
Use this procedure to upgrade the MicroTech III controller
application software and rmware.
Tools Required:
3/64ʺ (1 mm) Allen Key
Flat head screw driver to open control panel door
SD memory card no larger than 2GB for rmware less
than 8.46 (Click Here to Purchase)
SD memory card no larger than 8GB formatted to FAT32
for rmware greater than 8.46 (Click Here to Purchase)
SD memory card no larger than 32GB formatted to FAT32
for rmware 10.36 or greater (Click Here to Purchase)
NOTE: If the controller has a BSP version older than 8.40
or the APP version is earlier than 2506017300
contact Daikin Applied Technical Response group for
support.
Preparing the SD Card
1. To download the software code les online, navigate
http://www.daikinapplied.com.
2. Click on the Products tab. Then scroll down and click on
Controls. Click on the Resources tab. Under Application
Software, click on Controls.
3. Scroll down to nd the appropriate software version to
download and save it to the Desktop.
a. 2506017xxx represents Roofpack, Maverick
(MPS), and Self-Contained (SWP, SWT) code.
b. 2506018xxx represents Rebel (DPS) code
NOTE: (XXX) changes as the software versions are revised
for the respective product lines.
4. Drag the zip le to the freshly formatted SD card and e
4. xtract it to the root directory of the SD card. See picture
below as an example of where the zip le resides on the
SD card (E:\) directory.
NOTE: Every computer will have a dierent drive letter
designation for the SD card. Root directory
represents the rst location that appears when
opening the SD card since the MicroTech III controller
cannot see les from any folders. Zip le names
would change as mentioned in step 3 once new
software versions are released.
5. Once all the les are extracted there will be a total of 8
– 9 les appearing on the SD card. Total les counts can
change with new software revisions. The list below show
4 - 5 critical les needed for a software download.
HMI.ucf
MBRT.ucf
OBH.ucf
POL687.ucf
POL687.hex (omitted after 513 and 214 codes)
Complete list of les including all critical ones shown below
6. This completes preparing the SD card for the download
process and should now be taken to the MicroTech
controller.