Daikin EWWDC11CJYNN [23/180] Operating limits

Daikin EWWD480CJYNN [23/180] Operating limits
ESIE07-05 General Outline
Part 1 – System Outline 1–7
3
1
4
5
1.4 Operating Limits
Operating limits The table below gives the operating limits.
EWWD340-C19CJYNN R-134a
Max evaporator leaving water temperature 15 °C
Min evaporator leaving water temperature (without glycol) 4 °C
Min evaporator leaving water temperature (with glycol) -8 °C
Min evaporator water T4 °C
Max evaporator water T8 °C
Min T between leaving water evaporator and leav. water condenser 16 °C
Max T between leaving water evaporator and leav. water condenser 48 °C
Min condenser entering water temperature 15 °C
Max condenser leaving water temperature 55 °C
Min condenser water T (1 pass) 4 °C
Max condenser water T (1 pass) 8 °C