ESIE07-05 The Digital Controller
Part 2 – Functional Description 2–37
3
2
4
5
1
Delay low oil pressure alarm P STARTUP DELAY = 300 s
P OPERATING DELAY = 90 s
Delay high oil pressure differential 20 sec
Max differential oil pressure 2.5 bar
Freeze protection
P SETPOINT = 02.0 °C
P DIFFERENTIAL = 01.0 °C
Liquid Injection
P SETPOINT = 85.0 °C
P DIFFERENTIAL = 10.0 °C
Evaporator heater
P SETPOINT = 3.0 °C
P DIFFERENTIAL = 1.0 °C
Supervisor configuration
P PROTOCOL = CAREL
P COMMUNICATION SPEED = 19200
P IDENTIFICATION NUMBER = 001
Default parameter? NO
P Modem connection password
P Passwor for driver configuration
(Exv manufacture)
0152
Password for driver configuration Reserved area
Oil low pressure
alarm delays
Startup delay
Run delay
300
090
s
s
Oil high pressure
diff. delays
Setp
Delay
2.5
020
bar
s
Liquid injection
Setpoint
Diff.
085.0
10.0
˚C
˚C