Daikin EWWDC11CJYNN [52/180] Controller input output

Daikin EWWD480CJYNN [52/180] Controller input output
The Digital Controller ESIE07-05
2–14 Part 2 – Functional Description
3
1
2
4
5
1.4.6 Controller Input/Output
Introduction The software makes reference to the configuration of the input and output channels of the Microtech
II controller as shown in the tables below:
Compressor 1
COMPRESSOR 1
Connector Pin Type Futher information
J1 G/G0 powersupply power for controller
J2 B1/GND analog input evaporator entering water sensor
B2/GND analog input evaporator leaving water sensor
B3 analog input setpoint override
GND GND
+VDC power
J3 B4/BC4 analog input oil discharge PT1000 sensor
B5/BC5 analog input condensor leaving water sensor
J4 VG/VGO powersupply
Y1/VGO analog output analog output 0-10 VDC
J5 ID1 digital input on-off compressor switch
ID2 digital input flow switch (not installed)
ID3 digital input on-off remote unit auxiliary relay
ID4 digital input discharge thermal protector
ID5 digital input low pressure switch
ID6 digital input external fault (remove 323)
ID7 digital input phase monitor
ID8 digital input double setpoint (remove 322)
IDC1 powersupply
J6 B6/+VDC
(J2)/GND
analog input compressor load transducer
B7/+VDC
(J2)
analog input high pressure transducer
B8/+VDC
(J2)
analog input oil pressure transducer
GND GND