Daikin EWAT260B-SRB2 [40/62] Ewat b sl

Daikin EWAT420B-SSA2-VFDFAN [40/62] Ewat b sl
SOUND LEVELS
40/62
EWAT~B-SS
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Sound
Power
MODEL
63 Hz
125 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
db (A)
85
61.4
66.3
62.4
60.1
57.5
51.8
67.4
85
115
64.5
69.4
65.5
63.2
60.6
54.9
70.5
88
135
66.0
70.9
66.9
64.7
62.1
56.4
72.0
90
155
63.5
68.4
64.5
62.2
59.6
53.9
69.5
88
175
67.8
72.6
68.7
66.5
63.9
58.1
73.8
92
195
65.3
70.1
66.2
64.0
61.4
55.6
71.3
90
205
66.3
71.2
67.3
65.0
62.4
56.7
72.3
91
215
68.8
73.7
69.8
67.5
64.9
59.2
74.8
93
240
68.3
73.2
69.3
67.0
64.4
58.7
74.3
93
260
68.8
73.7
69.8
67.5
64.9
59.2
74.8
94
290
69.8
74.7
70.8
68.5
65.9
60.2
75.8
95
310
69.4
74.3
70.4
68.1
65.5
59.8
75.4
95
330
69.8
74.6
70.7
68.5
65.9
60.1
75.8
95
340
70.6
75.5
71.6
69.3
66.7
61.0
76.6
96
350
70.1
75.0
71.1
68.8
66.2
60.5
76.1
96
420
70.7
75.6
71.7
69.4
66.8
61.1
76.7
97
460
71.0
75.9
72.0
69.7
67.1
61.4
77.0
97
510
71.6
76.5
72.6
70.3
67.7
62.0
77.6
98
570
71.9
76.7
72.8
70.6
68.0
62.2
77.9
98
610
71.9
76.8
72.9
70.6
68.0
62.3
77.9
98
670
72.2
77.1
73.1
70.9
68.3
62.6
78.2
99
EWAT~B-SL
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Sound
Power
MODEL
63 Hz
125 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
db (A)
85
60.3
65.2
61.3
59.0
56.4
50.7
66.3
84
115
62.5
67.4
63.4
61.2
58.6
52.9
68.5
86
135
63.3
68.2
64.2
62.0
59.4
53.7
69.3
87
155
62.4
67.3
63.3
61.1
58.5
52.8
68.4
87
175
64.7
69.6
65.7
63.4
60.8
55.1
70.7
89
195
63.5
68.4
64.5
62.2
59.6
53.9
69.5
88
205
64.0
68.9
65.0
62.8
60.1
54.4
70.1
89
215
65.6
70.5
66.6
64.3
61.7
56.0
71.6
90
240
65.8
70.7
66.7
64.5
61.9
56.2
71.8
91
260
65.8
70.7
66.8
64.5
61.9
56.2
71.8
91
290
66.0
70.9
66.9
64.7
62.1
56.4
72.0
91
310
66.3
71.2
67.3
65.0
62.4
56.7
72.3
92
330
66.3
71.2
67.3
65.1
62.5
56.7
72.4
92
340
67.1
72.0
68.1
65.9
63.2
57.5
73.2
93
350
66.4
71.3
67.4
65.1
62.5
56.8
72.4
92
420
67.3
72.2
68.3
66.0
63.4
57.7
73.3
93
460
67.4
72.3
68.3
66.1
63.5
57.7
73.4
93
510
68.0
72.8
68.9
66.7
64.1
58.3
74.0
94
570
68.0
72.9
69.0
66.7
64.1
58.4
74.0
94
610
68.1
73.0
69.0
66.8
64.2
58.5
74.1
95
670
68.6
73.4
69.5
67.3
64.7
58.9
74.6
95
Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and
Eurovent 8/1 for Eurovent certified units. The certification refers only to the overall sound power level.
The sound data in the Octave band spectrum is for intended for reference only and not considering binding.
The sound pressure is calculated from the sound power level and are for information only and not considered binding.