OPTIONS (TECHNICAL DATA)
46/62
Available fan static pressure correction factors
EXTERNAL STATIC PRESSURE [Pa]
0
10
20
30
COOLING CAPACITY CORRECTION FACTOR
1
0.998
0.995
0.990
COMPRESSOR POWER INPUTCORRECTION FACTOR
1
1.006
1.010
1.020
REDUCTION OF MAX OPERATING AMBIENT TEMPERATURE [°C]
1
-0.3
-0.5
-1
The above table is valid for SILVER and GOLD series with standard and VFD driven fans. Application with more
than 30 Pa of external static pressure are not recommended. In case where external static pressure over 30
Pa is required special high ESP fans are required.
Maximum cable dimension
Model
Max cable size
Model
Max cable size
EWAT085B-SS(L)(R)A1
3x70mm²
EWAT085B-XS(L)(R)A1
3x70mm²
EWAT115B-SS(L)(R)A1
3x70mm²
EWAT115B-XS(L)(R)A1
3x70mm²
EWAT135B-SS(L)(R)A1
3x70mm²
EWAT145B-XS(L)(R)A1
3x70mm²
EWAT155B-SS(L)(R)A2
3x70mm²
EWAT180B-XS(L)(R)A2
3x95mm²
EWAT175B-SS(L)(R)A1
3x70mm²
EWAT185B-XS(L)(R)A1
3x70mm²
EWAT195B-SS(L)(R)A2
3x70mm²
EWAT200B-XS(L)(R)A2
3x95mm²
EWAT205B-SS(L)(R)A2
3x70mm²
EWAT220B-XS(L)(R)A2
3x120mm²
EWAT215B-SS(L)(R)A1
3x70mm²
EWAT230B-XS(L)(R)A1
3x120mm²
EWAT240B-SS(L)(R)A2
3x120mm²
EWAT250B-XS(L)(R)A2
3x120mm²
EWAT260B-SS(L)(R)A2
3x120mm²
EWAT280B-XS(L)(R)A2
3x240mm²
EWAT290B-SS(L)(R)A1
3x240mm²
EWAT300B-XS(L)(R)A1
3x240mm²
EWAT310B-SS(L)(R)A2
3x240mm²
EWAT310B-XS(L)(R)A2
3x240mm²
EWAT330B-SS(L)(R)A2
3x240mm²
EWAT320B-XS(L)(R)A2
3x240mm²
EWAT340B-SS(L)(R)A1
3x240mm²
EWAT360B-XS(L)(R)A1
3x240mm²
EWAT350B-SS(L)(R)A2
3x240mm²
EWAT370B-XS(L)(R)A2
3x240mm²
EWAT420B-SS(L)(R)A2
3x240mm²
EWAT430B-XS(L)(R)A2
3x240mm²
EWAT460B-SS(L)(R)A2
3x2x185mm²
EWAT470B-XS(L)(R)A2
3x2x185mm²
EWAT510B-SS(L)(R)A2
3x2x185mm²
EWAT540B-XS(L)(R)A2
3x2x185mm²
EWAT570B-SS(L)(R)A2
3x2x185mm²
EWAT600B-XS(L)(R)A2
3x2x185mm²
EWAT610B-SS(L)(R)A2
3x2x185mm²
EWAT660B-XS(L)(R)A2
3x2x185mm²
EWAT670B-SS(L)(R)A2
3x2x185mm²
EWAT700B-XS(L)(R)A2
3x2x185mm²
Heat recovery Units may be optionally equipped with heat recovery system. This system is made by a water
-cooled heat exchanger located on the compressors discharge pipe and a dedicated management of condensing
pressure.
To guarantee compressor operation within its envelope, units with heat recovery cannot operate with water
temperature of the heat recovery water lower than 25°C.
It is a responsibility of plant designer and chiller installer to guarantee the respect of this value (e.g. using
recirculating bypass valve).
Plant water content The cooled water distribution circuits should have minimum water content to avoid
excessive compressors start and stop. In fact, each time the compressor starts up, an excessive quantity of oil
goes from the compressor sump and simultaneously there is a rise in the temperature of the compressor motor’s
stator due to the inrush current during the start - up. To prevent damage to the compressors, have been
envisaged the application of a device to limit frequent stops and restarts.
During the span of one hour there will be no more than 10 starts of the compressor. The plant side should
therefore ensure that the overall water content allows a more constant functioning of the unit and consequently
greater environmental comfort.
The calculation of the water content should also consider the plant’s design parameters.
As a general indication the water content should not be less than 5 lt/kW on single circuit units and 2,5l/kW on
the twin circuit units.
Note: The indication is intended as a general guideline and not intended to substitute the evaluation made by
qualified technical personnel or by HVAC engineers. For more detailed analysis is better to consider the use of
other more detailed approach.
Water quality Before putting the unit into operation, clean the water circuit. Dirt, scales, corrosion debrits
and other material can accumulate inside the heat exchanger and reduce its heat exchanging capacity. Pressure
drop can increase as well, thus reducing water flow. Proper water treatment therefore reduces the risk of
corrosion, erosion, scaling, etc. The most appropriate water treatment must be determined locally, according to
the type of system and water characteristics. The manufacturer is not responsible for damage to or
malfunctioning of equipment caused by failure to treat water or by improperly treated water.
Содержание
- Air cooled chiller with scroll compressors 1
- Databook 1
- Ewat b 1
- Features and benefits 2
- Features and benefits 3
- Features and benefits 4
- Features and benefits 5
- Additional information related to f gas regulation eu no 517 2014 of the european parliament and of the council of 16 april 2014 on fluorinated greenhouse gases and repealing regulation ec no 842 2006 6
- Features and benefits 6
- Features and benefits 7
- Features and benefits 8
- Nomenclature 9
- Options 10
- Standard options supplied on basic units 10
- Mechanical options on request 11
- Options 11
- Options 12
- Electrical options on request 13
- Options options 14
- Installation options on request 15
- Options 15
- Other options on request 15
- Ewat b ss l 16
- Technical specification 16
- Ewat b ss l 17
- Technical specification 17
- Ewat b ss l 18
- Technical specification 18
- Ewat b ss l 19
- Technical specification 19
- Ewat b sr 20
- Technical specification 20
- Ewat b sr 21
- Technical specification 21
- Ewat b sr 22
- Technical specification 22
- Ewat b sr 23
- Technical specification 23
- Ewat b xs l 24
- Technical specification 24
- Ewat b xs l 25
- Technical specification 25
- Ewat b xs l 26
- Technical specification 26
- Ewat b xs l 27
- Technical specification 27
- Ewat b xr 28
- Technical specification 28
- Ewat b xr 29
- Technical specification 29
- Ewat b xr 30
- Technical specification 30
- Ewat b xr 31
- Technical specification 31
- Electrical specifications 32
- Ewat b ss l 32
- Electrical specifications 33
- Ewat b ss l 33
- Electrical specifications 34
- Ewat b sr 34
- Electrical specifications 35
- Ewat b sr 35
- Electrical specifications 36
- Ewat b xs l 36
- Electrical specifications 37
- Ewat b xs l 37
- Electrical specifications 38
- Ewat b xr 38
- Electrical specifications 39
- Ewat b xr 39
- Ewat b sl 40
- Ewat b ss 40
- Sound levels 40
- Ewat b sr 41
- Ewat b xs 41
- Sound levels 41
- Ewat b xl 42
- Ewat b xr 42
- Sound levels 42
- Amb t c 43
- Elwt c 43
- Ewat b s silver series 43
- Operating limits 43
- Units with multi v layout 43
- Units with single v layout 43
- Amb t c 44
- Elwt c 44
- Ewat b x gold series 44
- Multi v gold efficiency 44
- Options technical data 44
- Ref 3 ref 2 44
- Units with single v layout 44
- Air heat exchanger altitude correction factors 45
- Minimum glycol percentage for low air ambient temperature to prevent freezing of the hydraulic circuit 45
- Options technical data 45
- Water flow 45
- Water heat exchanger maximum maximum water δt 45
- Available fan static pressure correction factors 46
- Heat recovery 46
- Maximum cable dimension 46
- Options technical data 46
- Plant water conten 46
- Water quality 46
- Options technical data 47
- B c d e 48
- Ewat b s silver series single pump low lift 48
- Installations notes 48
- Multi v layout 48
- Single v layout 48
- Ewat b s silver series single pump high lift 49
- External pressure head kpa 49
- Installations notes 49
- Multi v layout 49
- Single v layout 49
- Water flow l s 49
- B c d e 50
- Ewat b s silver series twin pump low lift 50
- External static pressure kpa 50
- Installations notes 50
- Multi v layout 50
- Single v layout 50
- Water flow l s 50
- Ewat b x gold series single pump low lift 51
- External pressure head kpa 51
- External static pressure kpa 51
- H i j k 51
- Installations notes 51
- Multi v layout 51
- Single v layout 51
- Water flow l s 51
- Ewat b x gold series single pump high lift 52
- External pressure head kpa 52
- Installations notes 52
- Multi v layout 52
- Single v layout 52
- Water flow l s 52
- Ewat b x gold series twin pump low lift 53
- External static pressure kpa 53
- Installations notes 53
- Multi v layout 53
- Single v layout 53
- Water flow l s 53
- E i c b 54
- Ewat b x gold series twin pump high lift 54
- External pressure head kpa 54
- Installations notes 54
- Multi v layout 54
- Single v layout 54
- Water flow l s 54
- External pressure head kpa 55
- Installations notes 55
- Starting current with soft starter tank volume hydronic kit with tank 55
- Water filter pressure drops 55
- Installations notes 56
- Location 56
- Space requirements 56
- Warning 56
- Installations notes 57
- Multiple chillers installation closed area with wind prevalent direction 57
- Multiple chillers installation free field with wind prevalent direction 57
- Hydraulic schemes 58
- Installations notes 58
- Water filter 58
- Installations notes 59
- Technical specifications 59
- Installations notes 60
- Technical specifications 60
- Installations notes 61
- Technical specifications 61
Похожие устройства
- Daikin EWAT290B-SRA1 Технические данные
- Daikin EWAT290B-SRA1 Руководство по эксплуатации
- Daikin EWAT290B-SRA1 Инструкция по эксплуатации
- Daikin EWAT290B-SRA1 Инструкция по монтажу
- Daikin EWAT290B-SRB1 Технические данные
- Daikin EWAT290B-SRB1 Руководство по эксплуатации
- Daikin EWAT290B-SRB1 Инструкция по эксплуатации
- Daikin EWAT290B-SRB1 Инструкция по монтажу
- Daikin EWAT310B-SRA2 Руководство по эксплуатации
- Daikin EWAT310B-SRA2 Технические данные
- Daikin EWAT310B-SRA2 Инструкция по эксплуатации
- Daikin EWAT310B-SRA2 Инструкция по монтажу
- Daikin EWAT310B-SRB2 Технические данные
- Daikin EWAT310B-SRB2 Руководство по эксплуатации
- Daikin EWAT310B-SRB2 Инструкция по эксплуатации
- Daikin EWAT310B-SRB2 Инструкция по монтажу
- Daikin EWAT330B-SRA2 Технические данные
- Daikin EWAT330B-SRA2 Руководство по эксплуатации
- Daikin EWAT330B-SRA2 Инструкция по эксплуатации
- Daikin EWAT330B-SRA2 Инструкция по монтажу