INSTALLATIONS NOTES
For mutliple chiller installation it is recommended to install the chillers is a single row as hown in the picture
below
For additional information refer to the Installation Manual. If the site does not allow this kind of installation contact
Daikin representative to evaluate possible arrangements.
Multiple chillers installation free field with wind prevalent direction
Considering an installation in areas with prevailing wind direction (as represented in the first image below):
-
Chiller n.1: operates with no air overtemperature
-
Chiller n.2: operates in heated environment caused by Chiller n.1 and by itself
-
Chiller n.3: operates in partially heated environment caused by Chiller n.2
To reduce the effect of prevailing wind, it is opportune to set the chillers main dimension parallel to the wind prevailing
wind (as represented in the second image below).
Multiple chillers installation closed area with wind prevalent direction
In case of closed area with height equal or higher than the chillers, installation is the installation is not recommended.
Chillers 2 and 3 operate at significantly higher temperatures due to the higher recirculation. In this case it is necessary
to adopt special precautions based on the specific installation (for example: walls with grids, installation of the unit
on base to increase its height, duct on fans, high head fans, etc.)
Chiller
n.1
Chiller
n.2
Chiller
n.1
Chiller
n.3
Chiller
n.1
Chiller
n.2
Chiller
n.3