Daikin EWAT260B-SRB2 [53/62] Multi v layout

Daikin EWAT260B-SRB2 [53/62] Multi v layout
53/62
INSTALLATIONS NOTES
EWAT~B-X (GOLD SERIES) Twin pump low lift
Single-V layout
Pump
curve
Pump
motor
power
[kW]
Pump
motor
current
[A]
Pump
curve
Pump
motor
power
[kW]
Pump
motor
current
[A]
EWAT085B-XSA1
A
1,4
2,5
A
4,0
7,6
EWAT115B-XSA1
B
2,0
3,4
A
4,0
7,6
EWAT145B-XSA1
C
2,0
3,4
B
7,5
14,1
EWAT185B-XSA1
D
2,5
4,5
B
4,0
7,6
B
7,5
14,1
C
7,5
14,1
E
7,5
14,1
C
7,5
14,1
D
7,5
14,1
E
9,2
17,2
D
9,2
17,2
F
9,2
17,2
G
11
20,2
H
11
20,2
I
11
20,2
J
15
26,6
K
15
26,6
External static pressure refers to unit equipped with hydronic kit, defined as difference between pump external static pressure and
evaporator pressure drops. Water flow range refer to pump only. For water flow limits of the unit refer to water flow section.
To calculate the total electrical data of the base unit selected with hydronic kit, the electrical data of the pump must be added to the
electrical data of the base unit. Electrical data are subject to modification without notice. Please refer to unit nameplate.
0
20
40
60
80
100
120
140
160
180
200
0 2 4 6 8 10 12
External static pressure [kPa]
Water flow [l/s]
Single-V layout
B
C
D
A
0
50
100
150
200
250
300
0 5 10 15 20 25 30 35 40 45
External static pressure [kPa]
Water flow [l/s]
Multi-V layout
F
B
C
D
E
G
A
H
I
J
K

Содержание