Daikin UCJ850N [21/38] Ucpj100n

Daikin UCJ850N [21/38] Ucpj100n
19
20
(0.06)
25
(0.07)
33
(0.08)
Evap. air
AFR
(BF)
EWB
EDB
16.0
18.0
19.0
22.0
24.0
16.0
18.0
19.0
22.0
24.0
16.0
18.0
19.0
22.0
24.0
23.0
25.0
27.0
30.0
32.0
23.0
25.0
27.0
30.0
32.0
23.0
25.0
27.0
30.0
32.0
TC
9.0
9.7
10.1
11.4
12.5
9.8
10.5
11.0
12.4
13.6
10.3
11.0
11.6
13.1
14.2
SHC
6.5
6.5
6.9
6.9
7.0
7.4
7.3
7.9
7.9
7.9
8.5
8.4
9.1
9.1
9.1
WFC
28
30
31
35
38
30
32
34
38
41
32
34
35
40
43
PD
19.7
23.5
25.0
33.0
38.5
23.5
27.4
31.0
38.5
43.9
27.4
31.0
33.0
42.1
47.9
PI
1.8
1.9
1.9
2.0
2.0
1.9
2.0
2.0
2.0
2.1
2.0
2.0
2.1
2.1
2.3
TC
8.7
9.3
9.8
11.1
12.1
9.4
10.2
10.6
12.0
13.2
9.9
10.7
11.1
12.6
13.8
SHC
6.3
6.3
6.8
6.8
6.8
7.2
7.2
7.7
7.7
7.8
8.3
8.3
8.9
8.9
8.9
WFC
28
30
31
35
38
30
32
34
37
41
32
34
35
39
42
PD
19.7
23.5
25.0
33.0
38.5
23.5
27.4
31.0
37.2
43.9
27.4
31.0
33.0
40.4
45.8
PI
2.1
2.1
2.2
2.2
2.3
2.2
2.2
2.3
2.3
2.4
2.3
2.3
2.4
2.4
2.5
TC
8.4
9.0
9.4
10.7
11.6
9.1
9.8
10.2
11.6
12.6
9.6
10.3
10.7
12.2
13.3
SHC
6.2
6.2
6.6
6.6
6.7
7.0
7.0
7.5
7.6
7.6
8.1
8.1
8.7
8.8
8.8
WFC
28
30
31
35
37
30
32
33
37
40
32
34
35
39
42
PD
19.7
23.5
25.0
33.0
37.2
23.5
27.4
29.2
37.2
42.1
27.4
31.0
33.0
40.4
45.8
PI
2.4
2.5
2.5
2.6
2.6
2.5
2.6
2.6
2.7
2.7
2.6
2.7
2.7
2.8
2.8
TC
8.1
8.7
9.0
10.2
11.2
8.8
9.4
9.8
11.1
12.1
9.2
9.9
10.3
11.7
12.7
SHC
6.0
6.0
6.4
6.4
6.5
6.9
6.9
7.3
7.4
7.4
8.0
8.0
8.6
8.6
8.6
WFC
28
30
31
34
37
30
32
33
37
40
32
34
35
39
42
PD
19.7
23.5
25.0
31.0
37.2
23.5
27.4
29.2
37.2
42.1
27.4
31.0
33.0
40.4
45.8
PI
2.7
2.8
2.8
2.9
3.0
2.9
2.9
3.0
3.0
3.1
3.0
3.0
3.1
3.2
3.2
25.0
30.0
35.0 40.0
Leaving condenser water temperature (°C)
Notes:
1.Figures in show nominal capacities.
2.Capacity and condenser water flow rate are based on 5.5°C (10°F) temperature rise. There is
no need to correct capacity, if the temperature rise is within 5~9°C, but compute condenser
water flow rate (WFC') using the following formula.
WFC'WFC
However, limit condenser water flow rate to the range of figures for "Pressure drop through
condenser" shown on page 27.
3. Ratings shown are net capacities which do not include a deduction for evaporator fan
motorheat.
4. SHC is based on each EWB and EDB.
Add SHC to SHC.
SHC Capacity correction for SHC for other dry bulb temp.
0.2960AFR (m
3
/min)(1-BF)(DB-EDB)/860
5. Direct interpolation is permissible. Do not extrapolate.
Symbols:
AFR : Air flow rate (m
3
/min)
BF : Bypass factor
EWB : Entering wet bulb temp. (°CWB)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
WFC : Condenser water flow rate (l/min.)
PD : Pressure drop (kpa)
(Cooling water)
PI : Power input (compressor) (kW)
UCPJ100N
36
(0.12)
53
(0.15)
64
(0.16)
Evap. air
AFR
(BF)
EWB
EDB
16.0
18.0
19.0
22.0
24.0
16.0
18.0
19.0
22.0
24.0
16.0
18.0
19.0
22.0
24.0
23.0
25.0
27.0
30.0
32.0
23.0
25.0
27.0
30.0
32.0
23.0
25.0
27.0
30.0
32.0
TC
14.6
15.7
16.4
18.7
20.5
16.4
17.7
18.5
21.0
23.0
16.9
18.2
19.0
21.6
23.7
SHC
10.6
10.7
11.3
11.5
11.6
13.1
13.1
14.0
14.1
14.2
14.4
14.4
15.4
15.5
15.6
WFC
48
51
53
60
65
53
57
59
66
71
54
58
60
68
73
PD
29.7
33.1
35.2
43.8
50.0
35.2
40.0
42.5
52.1
60.3
36.3
41.2
43.8
55.2
63.9
PI
3.8
4.0
4.0
4.2
4.3
3.8
4.1
4.1
4.3
4.4
3.9
4.1
4.2
4.3
4.4
TC
14.5
15.7
16.3
18.5
20.5
16.3
17.6
18.3
20.8
23.0
16.8
18.1
18.8
21.4
23.7
SHC
10.6
10.7
11.3
11.4
11.6
13.0
13.0
13.9
14.0
14.2
14.3
14.3
15.4
15.4
15.6
WFC
49
52
54
60
65
54
57
59
66
72
55
59
61
68
74
PD
30.9
34.1
36.3
43.8
50.0
36.3
40.0
42.5
52.1
62.0
37.6
42.5
45.1
55.2
65.8
PI
4.2
4.3
4.3
4.5
4.6
4.2
4.3
4.4
4.6
4.7
4.3
4.4
4.4
4.6
4.7
TC
14.3
15.5
16.1
18.4
20.1
16.1
17.4
18.1
20.6
22.6
16.6
17.9
18.6
21.3
23.3
SHC
10.5
10.6
11.2
11.3
11.4
12.9
12.9
13.8
13.9
14.0
14.2
14.2
15.3
15.4
15.4
WFC
49
52
54
60
65
54
57
59
67
72
55
59
61
68
74
PD
30.9
34.1
36.3
43.8
50.0
36.3
40.0
42.5
53.7
62.0
37.6
42.5
45.1
55.2
65.8
PI
4.4
4.6
4.6
4.8
4.9
4.5
4.6
4.7
4.9
5.0
4.6
4.7
4.7
4.9
5.0
TC
14.0
15.2
15.8
17.9
19.8
15.8
17.0
17.7
20.1
22.3
16.3
17.5
18.3
20.7
22.9
SHC
10.3
10.4
11.1
11.1
11.3
12.8
12.8
13.7
13.7
13.9
14.1
14.1
15.2
15.2
15.3
WFC
49
52
54
60
65
54
57
59
66
72
55
59
61
68
74
PD
30.9
34.1
36.3
43.8
50.0
36.3
40.0
42.5
52.1
62.0
37.6
42.5
45.1
55.2
65.8
PI
4.7
4.8
4.9
5.1
5.2
4.8
4.9
5.0
5.2
5.3
4.9
5.0
5.1
5.2
5.4
25.0
30.0
35.0 40.0
Leaving condenser water temperature (°C)
UCPJ170P
54.5
(0.12)
80
(0.16)
96
(0.17)
Evap. air
AFR
(BF)
EWB
EDB
16.0
18.0
19.0
22.0
24.0
16.0
18.0
19.0
22.0
24.0
16.0
18.0
19.0
22.0
24.0
23.0
25.0
27.0
30.0
32.0
23.0
25.0
27.0
30.0
32.0
23.0
25.0
27.0
30.0
32.0
TC
21.9
23.6
24.6
28.0
30.7
24.3
26.2
27.3
31.1
34.1
24.8
26.7
27.9
31.7
34.8
SHC
16.0
16.0
17.0
17.2
17.4
19.4
19.4
20.8
20.9
21.0
21.2
21.2
22.8
22.9
23.0
WFC
72
77
80
89
97
79
85
88
98
106
80
86
90
100
109
PD
30.8
34.5
36.8
44.4
51.5
36.1
40.9
43.5
52.3
59.8
36.8
41.7
45.3
53.9
62.7
PI
5.7
6.1
6.1
6.3
6.5
5.9
6.2
6.3
6.5
6.7
6.0
6.4
6.5
6.7
6.9
TC
21.7
23.4
24.4
27.7
30.6
24.1
26.0
27.1
30.8
34.0
24.6
26.6
27.6
31.4
34.7
SHC
15.9
16.0
17.0
17.1
17.4
19.3
19.3
20.7
20.8
21.0
21.1
21.1
22.7
22.8
23.0
WFC
73
78
81
90
98
80
85
88
99
107
82
87
90
101
110
PD
31.6
35.3
37.6
45.3
52.3
36.8
40.9
43.5
53.2
60.8
38.4
42.6
45.3
55.1
63.8
PI
6.3
6.5
6.5
6.8
6.9
6.5
6.7
6.7
7.0
7.1
6.7
6.8
6.9
7.2
7.3
TC
21.5
23.2
24.1
27.5
30.2
23.9
25.7
26.8
30.6
33.5
24.3
26.2
27.3
31.2
34.2
SHC
15.8
15.9
16.8
17.0
17.2
19.2
19.2
20.6
20.7
20.8
21.0
21.0
22.6
22.7
22.8
WFC
74
78
81
91
98
80
86
89
99
107
82
87
90
101
109
PD
32.2
35.3
37.6
46.2
52.3
36.8
41.7
44.4
53.2
60.8
38.4
42.6
45.3
55.1
62.7
PI
6.7
6.9
7.0
7.3
7.4
6.9
7.1
7.2
7.5
7.6
7.1
7.3
7.4
7.7
7.8
TC
21.0
22.7
23.6
26.8
29.7
23.4
25.2
26.3
29.7
33.0
23.8
25.7
26.8
30.3
33.6
SHC
15.6
15.6
16.6
16.7
17.0
19.0
19.0
20.4
20.4
20.7
20.8
20.8
22.4
22.4
22.6
WFC
74
78
81
90
98
80
85
89
98
107
82
87
90
100
109
PD
32.2
35.3
37.6
45.3
52.3
36.8
40.9
44.4
52.3
60.8
38.4
42.6
45.3
53.9
62.7
PI
7.2
7.3
7.5
7.7
7.9
7.4
7.6
7.7
7.9
8.1
7.6
7.7
7.9
8.1
8.3
25.0
30.0
35.0 40.0
Leaving condenser water temperature (°C)
UCPJ250P
[60Hz]
5.5
Temp.rise

Содержание

Скачать