Daikin UCJ850N [6/38] Safety devices

Daikin UCJ850N [6/38] Safety devices
4
Model
Cooling capacity 50/60Hz (*1)
Cooling capacity 50/60Hz (*2)
Capacity steps
Casing/Color
Compressor
Refrigeration oil
Condenser
Evaporator
Evaporator fan
Refrigerant
Air filter (Factory set)
Electronic thermostat
Pipe connections
Dimensions
Weight (Operating weight)
Conversion formulae
kcal/h=kW҂860
Btu/h=kW҂3414
cfm=m
3
/min҂35.3
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
%
r.p.m.
R
R/min.
mm
m
2
m
3
/min.
cfm
kW
kg
mm
kg
UCJ2000N
193.5/213.9
660,650/730,300
166,400/184,000
189.6/209.6
647,300/715,600
163,100/180,300
100670
Hermetically sealed reciprocating
36T55TACS
36
2,900/3,450
36.1
Shell and cross fin tube
1CXCD2422
617/708
464
2.0
3.38
2D3C
540
19,100
11
R22
38.5
Thermal expansion valve
3
Resin net
2 steps
FPT3B
FPS1
1
/
4
B/FPS1B
1,8502,3601,200
1,360(1,391)
Unit size
Compressor thermal protector
Overcurrent relay (Comp.)
Overcurrent relay (Fan motor)
High pressure switch
Fusible plug
Reverse phase protector
100
170
250
335
500
670
850
1000
1320
1600
2000
Safety devices
The following safety devices are standard.
NOTES:
1. (*1) Cooling capacities are based on the following operating conditions:
Indoor air temp·······27°C DB, 19.5°C WB
(*2) Cooling capacities are based on the following operating conditions:
Indoor air temp·······27°C DB, 19.0°C WB
Leaving Condenser water temperature : 35°C
2. Cooling capacities are gross capacities which do not include a deduction for evaporator fan motor heat.
Type
No. Model
No. of cylinders
Speed 50/60Hz
Model
Charge
Type
No. Model
*1 Water flow
rate 50/60Hz
Coil
Row stage
Fin pitch
Face area
Type
Model
Drive
Air flow rate
50/60Hz
Motor output
Model
Charge
Control
No. of circuits
Condenser water inlet/outlet
Drain-Upper/lower
HWD
Cold rolled steel plate/Ivory white
SUNISO 4GS DID-K
Cross fin coil (Waffle louver fins and Hi-X tubes)
Dual suction multi-blade
Belt
[50/60Hz]

Содержание

Скачать