Daikin FXMQ50MVE Сервис мануал онлайн [102/254] 541322

Daikin FXYB63KV1 Сервис мануал онлайн [102/254] 544825
Si38-606 Field Setting
Test Operation 91
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory set
0
EMG (emergency
operation)
INV compressor
operation inhibited.
8777777
Normal operation
8777778
Emergency operation
8777787
1
Cool / Heat
Unified address
8777778
Address 0
8777777
Binary number 1
8777778
(6 digits) ~
31
8788888
2
Low noise/demand
address
8777787
Address 0
8777777
Binary number 1
8777778
(6 digits) ~
31
8788888
5 Indoor forced fan H
8777878
Normal operation
8777778
Indoor forced fan H
8777787
6
Indoor forced
operation
8777887
Normal operation
8777778
Indoor forced operation
8777787
8 Te setting
8778777
High
8777877
Normal (factory setting)
8777787
Low
8777778
9 Tc setting
8778778
High
8777877
Normal (factory setting)
8777787
Low
8777778
11
Sequential operation
setting
8778788
OFF
8777778
ON
8777787
12
External low noise/
demand setting
8778877
External low noise/demand:
NO
8777778
External low noise/demand:
YES
8777787
13 Airnet address
8778878
Address 0
8777777
Binary number 1
8777778
(6 digits) ~
63
8788888
18
High static pressure
setting
8787787
High static pressure setting:
OFF
8777778
High static pressure setting:
ON
8777787
19
Emergency
operation
(STD compressor is
inhibited to operate.)
8787788
OFF
8777777
STD 1, 2 operation: Inhibited
8777778
STD 2 operation: Inhibited
8777787
20
Additional refrigerant
operation setting
8787877
Refrigerant charging: OFF
8777778
Refrigerant charging: ON
8777787
21
Refrigerant recovery/
vacuuming mode
setting
8787878
Refrigerant recovery: OFF
8777778
Refrigerant recovery: ON
8777787
22
Night-time low noise
setting
8787887
OFF
8777777
Level 1 (outdoor fan with 6 step or lower)
8777778
Level 2 (outdoor fan with 5 step or lower)
8777787
Level 3 (outdoor fan with 4 step or lower)
8777788
25 Low noise setting
8788778
Level 1 (outdoor fan with 6 step or lower)
8777778
Level 2 (outdoor fan with 5 step or lower)
8777787
Level 3 (outdoor fan with 4 step or lower)
8777877

Содержание