Daikin FXMQ50MVE [98/254] Field setting from outdoor unit

Daikin FXD50MVE [98/254] Field setting from outdoor unit
Si38-606 Field Setting
Test Operation 87
3.2 Field Setting from Outdoor Unit
3.2.1 Field Setting from Outdoor Unit
Setting by dip switches
The following field settings are made by dip switches on PC board.
Setting by pushbutton switches
The following settings are made by pushbutton switches on PC board.
In case of multi-outdoor unit system, various items should be set with the master unit.
(Setting with the slave unit is disabled.)
The master unit and slave unit can be discriminated with the LED indication as shown below.
(Factory setting)
Dipswitch
Setting item Description
No. Setting
DS1-1
ON
Cool / Heat select
Used to set cool / heat select by remote controller
equipped with outdoor unit.
OFF (Factory set)
DS1-2
~DS1-4
ON
Not used Do not change the factory settings.
OFF (Factory set)
DS2-1
~4
ON
Not used Do not change the factory settings.
OFF (Factory set)
DS3-1,
2
ON
Not used Do not change the factory settings.
OFF (Factory set)
Caution
DIP switch Setting after changing the main P.C.Board(A1P) to spare parts P.C.B.
When you change the main P.C.Board(A1P) to spare parts P.C.B., please carry out the following
setting.
DIP Switch Detail
DS No. Item Contents
DS1-1 Cool/Heat change
over setting
ON The Cool/Heat change over setting is carried out by COOL/
HEAT changeover remote controller fitted to outdoor unit.
OFF
The Cool/Heat change over setting is not carried out by COOL/
HEAT changeover remote controller fitted to outdoor unit.
DS1-2 Domestic/Overseas
setting
ON Domestic Japan
OFF Overseas
DS1-3 Cooling only/Heat-
pump setting
ON Cooling only
OFF Heat-pump
DS1-4
Not used
OFF
Do not change the factory settings.
(Refrigerant classification)
DS2-1
OFF
DS2-2 HP setting
(Horse power)
DS2-3
DS2-4
1 2 3 4 1 2 3 4
DS1 DS2
ON
OFF
ON
OFF
810HP
DS2-2 OFF ON
DS2-3 ON ON
DS2-4 OFF OFF
H1P H2P H3P H4P H5P H6P H7P H8P
One outdoor
unit installed
7787777
7