Daikin FXMQ50MVE [70/254] Std compressor overload protection

Daikin FXA40LVE [70/254] Std compressor overload protection
Si38-606 Protection Control
Function 59
4.5 STD Compressor Overload Protection
This control is used to prevent abnormal heating due to overcurrent to the compressor resulting
from failures of STD compressor such as locking.
4.6 Crankcase Heater Control
Controls the crankcase heater to prevent refrigerant from remaining in the inverter and STD
compressor.
Td : Compressor discharge pipe temperature.
STD compressor ON
CT detection current value>15.0A
for more than 3 sec.
STD compressor OFF for 30 min.
Demand to operate.
When occurring 3 times within 90 minutes,
the malfunction code E6 is output.
Crank case
heater OFF
Crank case
heater ON
Td<70˚C during compressor stop
Td<75˚C
(V0833)