Si38-606 Field Setting
Test Operation 93
Setting item 0 Display contents of “Number of units for sequential start,
and others
No. Setting item
LED display
Data display
H1P H2P H3P H4P H5P H6P H7P
0
Number of units for sequential
starting, and others
9777777
See below
1 C/H unified address
9777778
Lower 6 digits
2 Low noise/demand address
9777787
3 Not used
9777788
4 Airnet address
9777877
5
Number of connected indoor units
*1
9777878
7
Number of connected zone units
(Fixed to 0)
9777888
8 Number of outdoor units *2
9778777
11
Number of zone units (excluding
outdoor and BS unit)
9778788
Lower 6 digits
12 Number of indoor units *3
9778877
Lower 4 digits:
upper
13 Number of indoor units *3
9778878
Lower 4 digits:
lower
14
Contents of malfunction (the
latest)
8778887
Malfunction
code table
Refer page
95.
15
Contents of malfunction
(1 cycle before)
8778888
16
Contents of malfunction
(2 cycle before)
8787777
20 Contents of retry (the latest)
8787877
21 Contents of retry (1 cycle before)
8787878
22 Contents of retry (2 cycle before)
8787887
The numbers in the “No.” column represent the number of times to press the SET (BS2) button.
EMG operation /
backup operation
setting
ON
9778777
OFF
9777777
Defrost select setting Short
9777877
Medium
9777977
Long
9777777
Te setting H
9777787
M
9777797
L
9777777
Tc setting H
9777778
M
9777779
L
9777777
c. Monitor mode
<Selection of setting item>
<Confirmation on setting contents>
To enter the monitor mode, push the
MODE button (BS1) when in
“Setting mode 1”.
Push the SET button (BS2) and set
the LED display to a setting item.
Push the RETURN button (BS3) to
display different data of set items.
Push the RETURN button (BS3) and
switches to the initial status of
“Monitor mode”.
Push the MODE button (BS1) and
returns to “Setting mode 1”.
(V2765)
*1: Number of indoor units
connected
Used to make setting of the
number of indoor units
connected to an out door unit.
*2: Number of outdoor units
connected
Used to make setting of the
number of outdoor units
connected to DIII-NET that is
one of the communication
lines.
*3: Number of terminal units
Used to make setting of the
number of indoor units
connected to DIII-NET that is
one of the communication
lines.
(Only available for VRV indoor
units)