Daikin FXMQ50MVE [159/254] Outdoor unit malfunction of thermistor r2t for suction pipe

Daikin FXMQ200MAVE [159/254] Outdoor unit malfunction of thermistor r2t for suction pipe
Troubleshooting by Indication on the Remote Controller Si38-606
148 Troubleshooting
2.26
J5
Outdoor Unit: Malfunction of Thermistor (R2T) for
Suction Pipe
Remote
Controller
Display
J5
Applicable
Models
RXM8, 10M
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the suction pipe temperature
thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the suction pipe temperature thermistor is detected.
Supposed
Causes
Defect of thermistor (R2T) for outdoor unit suction pipe
Defect of outdoor unit PC board (A1P)
Troubleshooting
: Refer to thermistor resistance / temperature characteristics table on P232.
(V3073)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
(R2T) from the outdoor
unit PC board.
(3.5k~
360k)
Replace outdoor unit PC board
(A1P).
Connect the thermistor and turn
on again.
NO
NO
Replace the thermistor (R2T).
YES
YES
Connector
is connected to
X37A, of outdoor unit
PC board.
(A1P)