Daikin FXAQ20MAVET Сервис мануал онлайн [127/264] 543605

Daikin FXAQ50MAVE Сервис мануал онлайн [127/264] 543603
Troubleshooting by Remote Controller SiBE34-703
116 Troubleshooting
8: ON 7: OFF 9: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No. Malfunction contents Page
Referred
Indoor Unit A0 999Error of external protection device 122
A1 999PC board defect, E
2
PROM defect 123
A3 999Malfunction of drain level control system (S1L) 124
A6 999Fan motor (M1F) lock, overload 126
A7 899Malfunction of swing flap motor (M1S) 127
A9 999Malfunction of moving part of electronic expansion
valve (Y1E)
129
AF 879Drain level above limit 131
AJ 999Malfunction of capacity setting 132
C4 999Malfunction of thermistor (R2T) for heat exchange
(loose connection, disconnection, short circuit, failure)
133
C5 999Malfunction of thermistor (R3T) for gas pipes (loose
connection, disconnection, short circuit, failure)
134
C9 999Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
135
CA 999Malfunction of thermistor for air inlet (loose
connection, disconnection, short circuit, failure)
136
CJ 898Malfunction of thermostat sensor in remote controller 137
Outdoor Unit E1 999PC board defect 138
E3 999Actuation of high pressure switch 139
E4 999Actuation of low pressure sensor 141
E5 999Compressor motor lock 143
E6 999Standard compressor lock or over current
E7 999Malfunction of outdoor unit fan motor 144
E9 999Malfunction of moving part of electronic expansion
valve (Y1E, Y2E)
145
F3 999Abnormal discharge pipe temperature 147
F6 999Refrigerant overcharged 148
H3 879Failure of high pressure switch
H4 999Actuation of low pressure switch
H7 999Abnormal outdoor fan motor signal
H9 999Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
149
J2 999Current sensor malfunction
J3 999Malfunction of discharge pipe thermistor (R2T) (loose
connection, disconnection, short circuit, failure)
150
J5 999Malfunction of thermistor (R3T, R5T) for suction pipe
(loose connection, disconnection, short circuit,
failure)
151
J6 999Malfunction of thermistor (R6T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
152
J7 999Malfunction of receiver outlet liquid pipe thermistor (R7T) 153
J9 999Malfunction of subcooling heat exchanger gas pipe
thermistor (R4T)
154
JA 999Malfunction of discharge pipe pressure sensor 155
JC 999Malfunction of suction pipe pressure sensor 156
L0 999Inverter system error
L1 999Malfunction of PC board 157
L4 999Malfunction of inverter radiating fin temperature rise 158
L5 999DC output overcurrent of inverter compressor 159
L8 999Inverter current abnormal 160
L9 999Inverter start up error 161

Содержание