Daikin FXHQ32MVET [15/370] In some models it is not possible to connect the maximum number of connectable indoor units select models so the total capacity of connected indoor units conforms to the specification

Daikin FXZQ25MVE [15/370] In some models it is not possible to connect the maximum number of connectable indoor units select models so the total capacity of connected indoor units conforms to the specification
SiBE311209 Model Selection
General Information 6
Indoor unit capacity
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (kW).
The total capacity of connected indoor units must be within a range of 50 to 130% of the
rated capacity of the outdoor unit.
In some models, it is not possible to connect the maximum number of connectable indoor
units. Select models so the total capacity of connected indoor units conforms to the
specification.
New refrigerant model
code
P15
type
P20
type
P25
type
P32
type
P40
type
P50
type
P63
type
P80
type
P100
type
P125
type
P140
type
P200
type
P250
type
Selecting model
capacity
1.7
kW
2.2
kW
2.8
kW
3.5
kW
4.5
kW
5.6
kW
7.0
kW
9.0
kW
11.2
kW
14.0
kW
16.0
kW
22.4
kW
28.0
kW
Equivalent output 0.6HP 0.8HP 1HP
1.25HP
1.6HP 2.0HP 2.5HP 3.2HP 4HP 5HP 6HP 8HP 10HP