SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 266
Troubleshooting Output current check
Refer to P.307.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
Is the stop
valve is
open?
Are the
compressor
lead wires
normal?
Are the wiring
and connection to
the compressor
normal?
Insulation
resistance of the
compressor is
100k
or less.
Compressor coils
are disconnected.
CHECK 4
Is the power transistor is
normal?
Error code “
L8
” is
displayed again.
Power OFF
NO
NO
NO
YES
YES
NO
YES
NO
Open the stop valve.
Replace the compressor
lead wires.
Correct the wiring and
connection.
Replace the inverter
compressor.
Replace the inverter
compressor.
Replace the inverter
PCB (A4P).
Continue the
operation.
Connect the compressor lead
wires then restart the operation.
Is the pressure difference
between high pressure and low
pressure before restarting
0.2MPa or less?
YES
YES
NO
Defective pressure
equalizing in the
refrigerant circuit.
Inspection of the
compressor.
YES
YES
NO
NO
CHECK 4