Daikin FXHQ32MVET [251/370] Troubleshooting

Daikin FXSQ80PVE4 [251/370] Troubleshooting
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 242
Troubleshooting
Note:
1: Make measurement of resistance between the connector pins, and then make sure the resistance falls in the
range of 40 to 50.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Turn power supply OFF, and
turn power supply ON again.
Return to normal?
YES
External factor other than error
(for example, noise etc.).
Check the electronic expansion valve corresponding to the error code “
E9
” in the monitor mode.
{
When Confirmation of error 4 shows as follows:
Electronic expansion valve for main use (Y1E) or electronic expansion valve for liquid injection (Y1E)
{
When Confirmation of error 4 shows as follows:
Electronic expansion valve for refrigerant charge (Y2E) or 2 stage selection 1 electronic expansion valve (Y2E1)
{
When Confirmation of error 4 shows as follows:
Electronic expansion valve for subcooling (Y3E) or 2 stage selection 2 electronic expansion valve (Y2E2)
{
Explanation of “
Master unit
Slave unit
Function unit
The connector of
outdoor unit PCB
(A1P) for electronic
expansion valve is
connected.
The coil resistance of
electronic expansion
valve is normal.
(
1)
NO
Ensure the correct connection.
NO
NO
YES
YES
Replace the coil of electronic
expansion valve.
Replace the outdoor unit PCB
(A1P).
(Orange) 1
(Red) 2
(Yellow) 3
(Black) 4
5
COM[+] (Gray) 6
Measuring points
1 - 6
2 - 6
3 - 6
Judgement criteria
40~50
4 - 6