Daikin RXQ18PY1 [123/355] Image of operation in the case of a and b

Daikin RXQ32PY1 [123/355] Image of operation in the case of a and b
SiEN34-705 Test Operation
General Information 117
Image of operation in the case of A
Image of operation in the case of B
Image of operation in the case of A and B
Operation sound during low
noise mode is instructed can
be set with “External low
noise level setting”
(Factory setting is “Mode 2”.)
Rated operation
sound
Operation sound
Approx. 50 db (target)
(The power consumption may be
increased by about 20%)
Approx. 45 db (target)
(The power consumption may be
increased by about 30%)
Note1: Above values are reference only (measured in silent room)
Note2: Above values are for 1 module only.
Operation sound of
level 2
Operation sound of
level 1
Operation sound of
level 3
Approx. 55 db (target)
(The power consumption may be
increased by about 10%)
If capacity precedence is set in
“Capacity precedence setting”, the
fan speed will be increased
according to the load of air
conditioning when load is heavier.
Low noise mode instructing
Operation sound level set with “External low noise setting”
Operation sound
of level 2
Operation sound
of level 1
Operation sound
of level 3
Operation sound
Rated operation
sound
Time set with “Night-time low noise start setting”
If capacity precedence is set in “Capacity
precedence setting”, the fan speed will be
increased according to the load of air
conditioning when load is heavier.
Time set with “Night-time low noise end setting”
Operation sound during
night-time low noise mode
is instructed can be set with
“Night-time low noise level
setting”.
(Factory setting is “OFF”.)
Set with “Night-time low noise end setting”
(Factory setting is “AM 8:00”.)
AM 8:00
AM 7:00
AM 6:00
Set with “Night-time low noise start setting”.
(Factory setting is “PM 10:00”.)
Night time
Operation sound level set with
“Night-time low noise setting”.
PM 0:00PM 8:00 PM 10:00
Operation sound
of level 2
Operation sound
of level 1
Operation sound
of level 3
Operation sound
Rated operation
sound
Time set with “Night-time low noise start setting”
If capacity precedence is set in “Capacity
precedence setting”, the fan speed will be
increased according to the load of air
conditioning when load is heavier.
Time set with “Night-time low noise end setting”
Operation sound during low noise
mode is instructed can be set with
“External low noise level setting”.
(Factory setting is “Mode 2”.)
Operation sound during night-time
low noise mode is instructed can
be set with “Night-time low noise
level setting”.
(Factory setting is “OFF”.)
Set with “Night-time low noise end setting”
(Factory setting is “AM 8:00”.)
AM 8:00
AM 7:00
AM 6:00
Set with “Night-time low noise start setting”.
(Factory setting is “PM 10:00”.)
Night time
* Operation sound level set with
“External low noise setting”.
PM 0:00
PM 8:00
PM 10:00
Low noise mode
instructing
When external low noise
instructed is received during
the operation with night-time
low noise mode,
Mole 2 precedes Level 1 and
Level 3 precedes Level 2.
* Operation sound
level set with
“Night-time low noise
setting”.
Low noise mode instructing
Operation sound set with
“External low noise setting”