Daikin RXQ18PY1 [81/355] No limit to wall height no limit to wall height

Daikin RXQ18PY1 [81/355] No limit to wall height no limit to wall height
SiEN34-705 Installation
General Information 75
3.2.12 Selection of Location
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial
environment. If installed as a household appliance it could cause electromagnetic interference.
The VRV outdoor units should be installed in a location that meets the following requirements:
1. The foundation is strong enough to support the weight of the unit and the floor is flat to
prevent vibration and noise generation.
2. The space around the unit is adequate for servicing and the minimum space for air inlet and
air outlet is available. (Refer to below figure and choose one of both possibilities.)
3. There is no danger of fire due to leakage of inflammable gas.
4. Ensure that water cannot cause any damage to the location in case it drips out the unit (e.g.
in case of a blocked drain pipe).
5. The piping length between the outdoor unit and the indoor unit may not exceed the allowable
piping length. (See “Example of connection”.)
6. Select the location of the unit in such a way that neither the discharged air nor the sound
generated by the unit disturb anyone.
7. Make sure that the air inlet and outlet of the unit are not positioned towards the main wind
direction. Frontal wind will disturb the operation of the unit. If necessary, use a windscreen to
block the wind.
Caution 1. An inverter air conditioner may cause electronic noise generated from AM broadcasting.
Examine where to install the main air conditioner and electric wires, keeping proper
distances away from stereo equipment, personal computers, etc.
If the electric wave of AM broadcasting is particularly weak, keep distances of 3m or more
and use conduit tubes for power and transmission lines.
2. In heavy snowfall areas, select an installation site where snow will not affect operation of the
unit.
3. If condensate may drip on downstairs (walkway) depending on the floor condition, take a
measure such as the installation of central drain pan kit (sold separately).
4. The refrigerant R-410A itself is nontoxic, nonflammable and is safe. If the refrigerant should
leak however, its concentration may exceed the allowable limit depending on room size. Due
to this it could be necessary to take measures against leakage. Refer to the chapter “Caution
for refrigerant leaks”.
10
10
10
20
20
10
50
50
50
200
400 400
50
10
300 300
300
500
500
500500
100
100
100
100
300
<
If installed as a single unit
>
(Pattern 1)
(Pattern 2)
(Pattern 3)
(Pattern 1)
(Pattern 2)
(Pattern 3)
<
When installed in serial
>
Front
side
Front
side
Front
side
Front
side
Front
side
Front
side
No limit to wall height
No limit to
wall height
Service space of
suction side
Service space of
front side
Service space of
suction side
Service space of
front side
Service space of
suction side
Service space of
front side
Service space of
front side
Service space of
suction side
1500
500
h1
h2
Front side
Suction side
B
A
h1 = A (Actual height) – 1500
h2 = B (Actual height) – 500
If this height is exceeded, calculate h1
and h2 shown in the figure below, and
add the service space for the front
and suction sides to h1/2 and h2/2.
For Patterns 1 and 2 in figure :
Wall height for front side no higher than
1500 mm.
Wall height on the suction side no higher
than 500 mm.
Wall height for sides – no limit.
1500
(mm)
1000
1000
1000
1500
1500
1500
indoor unit
Branch switch,
overcurrent breaker
personal computer or radio
remote
control
COOL / HEAT
selector
Branch switch,
overcurrent breaker