Daikin RXQ18PY1 [168/355] Pipe size reduce

Daikin RXQ48PY1 [168/355] Pipe size reduce
Appendix SiEN34-705
162 General Information
7.10.3 Reducer
7.10.4.1 Pipe size reducer (For R-410A)
KHRP26M73TP • 73HP
KHRP25M72TP • 73TP • 72HP
! This includes the following parts.
! This kit is the reducer of the branch piping kit (refnet joint • header).
Check the proper model of the branch piping kit.
Installation procedure
Refer to the installation manual of the branch piping kit.
! Joint size are as follows
(1) Select the field piping size according to the installation manual of the outdoor unit.
(2) Connect the PIPE SIZE REDUCER suitable for the field piping size to the branch piping kit.
ex.) Connect the reducers to the branch piping kit. KHRP26M73T.
• For inlet piping size
is Ø 41.3 and outlet 1 piping size is Ø 34.9
3P113129A
pipe size reducer
1
pipe size reducer
2
pipe size reducer
3
pipe size reducer
4
pipe size reducer
5
SHAPE
Quantity
KHRP26M73TP 1pc. 1pc. 2pc. ⎯⎯
KHRP26M73HP 1pc. 1pc. ⎯⎯
KHRP25M72TP ⎯⎯⎯1pc. 1pc.
KHRP25M72HP
⎯⎯⎯⎯1pc.
KHRP25M73TP 1pc. 1pc. 3pc. 1pc.
Kit name Branch piping kit
KHRP26M73TP
KHRP26M73T (gas side)
KHRP26M73HP
KHRP26M73H (gas side) • KHRP25M73H (suction gas side)
KHRP25M72TP
KHRP25M72T (discharge gas side)
KHRP25M72HP
KHRP25M72T (discharge gas side)
KHRP25M73TP
KHRP25M73T (suction, discharge side)
pipe size reducer
1
pipe size reducer
2
pipe size reducer
3
pipe size reducer
4
pipe size reducer
5
Field
piping
side
I.D. ø41.3
O.D. ø38.1
Field
piping
side
I.D. ø41.3
O.D. ø38.1
O.D. ø31.8
Field
piping
side
I.D. ø34.9
O.D. ø31.8
Field
piping
side
I.D. ø28.6
O.D. ø25.4
O.D. ø19.1
Field
piping
side
I.D. ø28.6
O.D. ø25.4
Pipe size reducer
Inlet
Outlet 1
Outlet 2
Field piping
ø41.3
Connections
I.D. ø38.1
Pipe size reducer
Field piping
ø34.9
Connections
Cut at the center
of the connections
with a pipe cutter
I.D. ø31.8
KHRP26M73T
(Gas side)