40 FDBG-A Series
14.1.4 Pump Down Operation method
R71FU
Take the following steps to perform the pumping-down operation.
Note: A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.
Caution to be taken when brazing refrigerant piping
“Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux”.
(Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based
flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the
refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible.)
(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing
temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g . BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant leakage.
C : 1PN01324A-2
Procedure Precautions
1. Connect a pressure gauge to the service port of the
stop valve.
Carry out an air purge of the charge hose.
2. Perform fan operation by the remote controller. Make sure that the liquid-side and gas-side stop valves
are fully open.
3. Perform cooling operation by the remote controller. Check that the compressor and outdoor fan are
operation.
4. Run the unit for one minute until the operation
stabilizes.
5. Close the liquid-side stop valve fully. (Refer to Fig.1) If the valve is not fully closed it could cause burn-out of
the compressor.
6. After the pressure gauge indication has dropped to 0
kgf/cm
2
G, close the gas stop valve fully and press the
Stop button on the remote controller.
This is the end of pumping-down operation.
After pumping-down operation, the remote controller
shows “U4” even when ON button on the remote controller
is pressed, and it will not operate. Although the remote
controller may or may not indicate “U4” according to
circumstances at this time, it is normal. When the remote
controller indicates “U4”, the indoor unit fan may operate
(for about max 30 minutes). Turn off the main power
supply switch and turn it on again in need of operation
.
Necessity of a trap Trap installation spacing
Since there is fear of the oil held inside the riser piping
flowing back into the compressor when stopped and
causing liquid compression phenomenon, or cases of
deterioration of oil return, it will be necessary to provide a
trap at an appropriate place in the riser gas piping.
Oil trap
Gas piping
Liquid piping
Indoor unit
Outdoor unit