Daikin FDBG71AVE [43/50] Installing the outdoor unit

Daikin FDBG50AVE [43/50] Installing the outdoor unit
Installation ED41-015B
42 FDBG-A Series
INSTALLING THE OUTDOOR UNIT
Applicable models: 25 to 60
For models 71, see the installation manual attached to the outdoor unit.
4 Selecting the Location
Select an installation site that fulfills the following conditions and meets the customers approval.
It is well-ventilated.
It is safe and can withstand the unit’s weight and vibration. The unit can be installed on a level surface.
The unit does not bother next-door neighbors.
There is no possibility of a flammable gas leak.
The water draining from the outdoor unit will not damage anything.
Sufficient clearance for servicing is ensured.
R25 · R35 · R50 · R60 R25 · R35
(One side facing one wall)
(Two sides facing two walls) R50 · R60
Units: mm
Dimension A
H = 1000 mm or less 300
H = 1000 mm or more 600
50 mm
or more
150 mm
or more
300 mm
or more
50 mm
or more
100 mm
or more
50 mm
or more
150 mm
or more
50 mm
or more
100 mm
or more
50 mm
or more
150mm
or more
H
H: The height of the
wall on the side that
air is discharged.
A mm
or more
(Three sides facing three walls)
Vinyl tubes
Water level
3 Indoor Unit Installation
While installing unit, Take care that dust etc. should not drop into the
drainpan.
Temporarily install the indoor unit.
Attach the hanger brackets to the suspension bolts. Be sure to use nuts and
washers both above and below the hanger brackets to secure them.
Use a water level or water-filled vinyl tubes to check that the unit is
level at all four corners as shown in the drawing.
Tighten the top nuts.
Nut (commercially available)
Tighten
(two nuts)
W
asher 6
C : 1PN04069-1A-2