Daikin CDKS35BVMB [122/179] Check no refer to p 29

Daikin 2AMKS40BVMB [122/179] Check no refer to p 29
SiBE12-314 Troubleshooting
Service Diagnosis 113
Troubleshooting
Check No.6
Refer to P.129
P4 : Radiation fin thermistor
J3 : Discharge pipe temperature thermistor
J6 : Outdoor unit heat exchanger temperature thermistor
J8 : Liquid pipe temperature thermistor
J9 : Gas pipe temperature thermistor
H9 : Outdoor air temperature thermistor
Turn on the power again.
Reconnect.
Reconnect.
Replace defective one(s) of
the following thermistors.
l
Radiation fin thermistor
l
Discharge pipe
temperature thermistor
l
Outdoor unit heat
exchanger temperature
thermistor
l
Liquid pipe temperature
thermistor
l
Gas pipe temperature
thermistor
l
Outdoor air temperature
thermistor
Replace the following
thermistor.
l
Indoor unit heat
exchanger thermistor
Replace the outdoor unit
PCB. (Replace the indoor
unit PCB.)
(R3043)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Error displayed again
on remote controller?
NO
YES
YES
YES
NO
Indoor unit
heat exchanger thermistor
functioning?
NO
Connector or thermistor
disconnected?
NO
YES
Normal?
Check No. 6
Check the thermistor resistance
value.
Check No. 6
Check the indoor unit heat
exchanger thermistor resistance
value in the heating mode.