Daikin EHSXB04P30A — установка и подключение систем управления отоплением и охлаждением [29/68]

Daikin EHSX04P30A [29/68] X set up and installation
Key names
Short
designation
Explanation Short
designation
Explanation
RoCon BM1
J9 Plug connection FLS (t
R1
/ V1) SG
Switching contact for Smart Grid (intelligent mains
co
nnection)
J10
Plug connection internal cabling
(to A1P)
TRA1 Transformer
J11
Plug connection internal cabling
(to RTX-AL4)
t
AU
External temperature sensor (RoCon OT1)
J12 Plug connection 3UV DHW t
DHW1
Storage tank temperature sensor 1 (RoCon BM1)
J13 Plug connection System-Bus (e.g. room station) t
DHW2
2 (A1P) storage tank temperature sensor
J14 Plug connection circulation pump P
Z
t
R1
Return flow temperature sensor 1 (FLS - RoCon
BM1)
J15 Plug connection internal cabling (strapping plug) t
R2
2 (A1P) return flow temperature sensor
J16
Plug connection room thermostat (EKRTR /
EKRTW)
t
V1
Flow temperature sensor 1 (RTX-AL4)
EHS157068 Mixer module t
V2
2 (A1P) flow temperature sensor
EHS157034 Room station t
V, BH
Flow temperature sensor Backup Heater (A1P)
Cooling out-
put
Output status for "Cooling" operating mode
V1 Flow sensor (FLS - RoCon BM1)
RT Room thermostat (EKRTW) XAG1 Plug connection exterior heat pump unit
RT-E Receiver for radio room thermostat (EKRTR) XBUH1 Plug connection backup heater (EKBUxx)
RTX-AL4 Switch board (interface) X2M6 Connecting cable clamp HPc-VK-1
RTX-AL4
J1 Plug connection to TRA1 X2M7 Connecting cable clamp HPc-VK-1
J3 Plug connection internal cabling (to A1P) X11M Terminal block in FWXV(15/20)AVEB
J6 Plug connection flow temperature sensor t
V1
RTX-EHS Switch board (Backup heater)
RTX-EHS
K1 Relay 1 for backup heater
K2 Relay 2 for backup heater
K3 Relay 3 for backup heater
X1
Terminal block for mains connection to backup
h
eater
X2_1
Plug connection internal cabling (to XBUH1)X2_2
X2_3
X3 Plug connection internal cabling to J3 (RTX-AL4)
Tab. 3-4 Key names for connections and circuit diagrams - Part 2
3 x Set-up and installation
Daikin Altherma EHS(X/H)
Daikin Solar tank with integrated interior heat pump unit
008.1420744 – 06/2015
Installation and maintenance manual
29
3.5 Laying coolant lines
Check whether oil trap arc necessary.
Required if Daikin Altherma EHS(X/H) is not installed at
ground level with the heat pump exterior unit (fig. 3-36,
H
O
10 m).
At least one oil trap arc must be installed every 10 m dif-
ference in height (fig. 3-36, H = clearance from oil trap arc
to oil trap arc).
Oil trap arc only required in gas line.
In
stall lines with bending unit and an adequate clearance to
electrical lines.
Only
solder with light nitrogen flow
(hard soldering only).
Do not apply heat insulation to joins until after start-up (for
purposes of leakage search).
Esta
blish flange connections and connect to the units.
( Pay attention to the tightening torque, see chapter 9.3
"Tightening torque").