Daikin EHSXB04P30A — installation and Maintenance Guide for Heating Systems [46/68]

Daikin EHSH16P50A [46/68] X errors malfunctions and messages
Installation and maintenance manual
46
Daikin Altherma EHS(X/H)
Daikin Solar tank with integrated interior heat pump unit
008.1420744 – 06/2015
7 x Errors, malfunctions and messages
Cooling effect of
room cooling insufficient
Water flow too low.
C
heck that all stop valves of the water circuit are
completely open.
Ch
eck that the water filter is dirty.
Check that the expansion tank is defective.
Fully vent the heating system and device-internal
circulation pump.
On th
e control unit (rotary switch position "Info" )
check that there is sufficient water pressure (>0.5 bar),
if necessary, refill the heating water.
Ch
eck that the resistance in the water circuit is not too
high for the pump (see installation manual for
"Technical Data").
Water quantity in heating system too low.
Ch
eck the primary pressure in the expansion
container and the water pressure, if necessary, refill
the heating water and reset the primary pressure
(see chapter 6.5).
Quantity of coolant in the heating system too
low or to
o high.
Determine the cause for the coolant being too low or
too high in the coolant circuit.
If the quantity of coolant is too low, check the cool-
ant circuit for leaks, repair and top up the coolant.
If the quantity of coolant is too great, recycle the
coolant and refill the system with the correct vol-
ume.
Device-internal circula-
tion pump is excessively
noisy whi
le running
Air in the water circuit
Fully vent the heating system and device-internal
circulation pump.
Noises caused by vibrations.
Ch
eck the Altherma EHS(X/H), its components and
covers to ensure they are fastened correctly.
Bearing damage in the device-internal circula-
tion pump.
Reduce pump speed [Min Perform Pump] and [Max
Perform Pump]).
Re
place device-internal circulation pump.
Water pressure at pump inlet too low.
On the controller (rotary switch setting "Info" )
check whether there is adequate water pressure
(>0.5 bar).
Ch
eck that the pressure gauge is working correctly
(connect an external pressure gauge).
Ch
eck the primary pressure in the expansion
container and the water pressure, if necessary, refill
the heating water and reset the primary pressure
(see chapter 6.5).
Safety pressure relief
valve is leaking or always
open.
Expansion tank is defective.
Re
place expansion tank.
Water pressure in the heating system is
too
high.
On the control unit (rotary switch position "Info" )
check that the water pressure lies beneath the stated
maximum pressure. If necessary, bleed the water until
the pressure lies in central permissible range.
Safety pressure relief valve is stuck.
Ch
eck safety pressure relief valve and if necessary,
replace it.
Turn the red knob on the safety pressure relief
valve counterclockwise. If you can hear a rattling
noise, the safety pressure relief valve needs
replacing.
Tab. 7-1 Possible malfunctions of the Altherma EHS(X/H)
Malfunction Possible cause Possible solution