Daikin Altherma EHS(X/H)
Daikin Solar tank with integrated interior heat pump unit
008.1420744 – 06/2015
Installation and maintenance manual
5
1.3 Avoid danger
The Daikin Altherma EHS(X/H) is state-of-the-art and is built to
meet all recognised technical requirements. However, improper
use can lead to serious injuries or death, as well as causing ma-
terial damage.
To prevent such risks, install and operate Daik
in Altherma
EHS(X/H) only:
– as stipulated and in perfect condition,
– with an awareness of the safety and hazards involved.
This assumes knowledge and use of the contents of this manual,
the
relevant accident prevention regulations and the recognised
safety-related and occupational medical rules.
WARNING!
This unit is not intended for use by persons (including
ch
ildren) with impaired physical, sensory or mental
faculties or persons with insufficient experience and/or
expertise unless supervised by a person responsible
for ensuring their safety or are given instruction by this
person on how to use the unit.
1.4 Intended use
The Daikin Altherma EHS(X/H) may only be used for preparation
of warm water, as a room heating system, and depending on its
design, as a room cooling system.
The Daikin Altherma EHS(X/H) must be installed, connected and
o
perated only according to the indications in this manual.
Only use of a suitable external unit approved by Daikin is per-
mitted. The following combinations are permissible in this re-
spect:
Internal unit External unit
Heating and
cooling (X)
Heating only (H)
EHSX04P30A EHSH04P30A
ERLQ004CAV3
EHSXB04P30A EHSHB04P30A
EHSX08P30A EHSH08P30A
ERLQ006CAV3
ERLQ008CAV3
EHSXB08P3
0A EHSHB08P30A
EHSX08P5
0A EHSH08P50A
EHSXB08P50A EHSHB08P50A
EHSX16P50A EHSH16P50A ERLQ011CA(V3/W1)
ERLQ014CA(V3/W1)
ERLQ016CA(V3/W1)
EHSXB16P5
0A
EHSHB16P50
A
B -
Additional heat exchanger for the bivalent connection
* Not all the equipment mentioned here is offered in some countries because of
the various different country-specific connection conditions.
Tab. 1-1 Permissible combinations of Daikin Altherma EHS(X/H)
internal units and Daikin heat pump external units
Any other use outside the intended use is considered as im-
proper. The operator alone shall bear responsibility for any re-
sulting damage.
Use as intended also involves compliance with maintenance and
inspection conditions. Spare parts must at least satisfy the tech-
nical requirements defined by the ma
nufacturer. This is the case,
for example, with original spare parts.
1.5 Instructions for operating safety
1.5.1 Before working on the hydraulic system
● Work on the Daikin Altherma EHS(X/H) (such as setup,
servicing, connection and initial start-up) is only to be carried
out by persons who are authorised and who have success-
fully completed qualifying technical or vocational training and
who
have taken part in advanced training sessions recog-
nised by the appropriate responsible authorities for the
spe
cific activity. This, in particular, includes heating
specialists and climate control technicians who have
experience, as a result of their technical training and their
knowledge of the subject, of proper and appropriate instal-
lation and maintenance of heating, climate control and
cooling installations and heat pumps.
● Switch off the external
main switch before starting any work
on the Daikin Altherma EHS(X/H) and secure it against
unintentional switch-on.
● Sea
ls must not be damaged or removed.
● Make sure that the safety valves comply with the require-
ments of EN 12828 when connecting on the heating side, and
with the requ
irements of EN 12897 when connecting on the
domestic water side.
● Only origi
nal Daikin replacement parts may be used.
1.5.2 Electrical installation
● Electrical installation may be carried out only by electrical
engineers and in compliance with the valid electro-technical
guidelines as well as the regulations of the relevant energy
supply company (EVU).
● Comp
are the mains voltage (~230 V, 50 Hz or ~400 V, 50 Hz)
indicated on the type plate with the supply voltage before
connecting to the mains.
● Before be
ginning work on live parts, disconnect all of the
systems circuits from the power supply (switch off main
switch, disconnect fuse) and secure against unintentional
restart.
● Equ
ipment covers and service panels must be replaced as
soon as the work is completed.
Содержание
- Indoor unit for air water heat pumps daikin altherma integrated solar unit p.1
- Installation and maintenance manual p.1
- Malfunctions 43 p.3
- Tightening torque 63 p.3
- Emergency operation 54 p.3
- Temporary shutdown 35 p.3
- List of keywords 67 p.3
- Electrical connection 7 p.3
- Technical data 58 p.3
- List of contents p.3
- Dimensions and connections 3 p.3
- Start up 31 p.3
- Laying coolant lines 29 p.3
- Design and components p.3
- Set up and installation 13 p.3
- Intended use p.3
- Decommissioning 35 p.3
- Set up 5 p.3
- Instructions for operating safety p.3
- Circuit diagram daikin altherma ehs x h 64 p.3
- Service and maintenance 38 p.3
- Initial commissioning 31 p.3
- Characteristic lines 61 p.3
- Safety 4 p.3
- Hydraulic system connection 55 p.3
- Avoid danger p.3
- Removing the protective cover 38 p.3
- General 38 p.3
- Activities to be performed annually 38 p.3
- Recognising errors correcting malfunctions 42 p.3
- Final shutdown 37 p.3
- Filling the system with water 30 p.3
- Re commissioning 33 p.3
- Filling and topping up the storage tank 40 p.3
- Product description 7 p.3
- Filling and topping up the heating system 41 p.3
- Pressure test and filling the coolant circuit 30 p.3
- Fault codes 47 p.3
- Observing instructions p.3
- Errors malfunctions and messages 42 p.3
- Water connection 6 p.3
- Notes 65 p.3
- Warning signs and explanation of symbols p.3
- Monitoring and configuration dip switch 53 p.3
- Equipment data 58 p.3
- X safety p.4
- Warning signs and explanation of symbols p.4
- Validity p.4
- Special warning signs p.4
- Safety p.4
- Relevant documents p.4
- Observing instructions p.4
- Meaning of the warnings p.4
- Handling instructions p.4
- Intended use p.5
- Instructions for operating safety p.5
- Electrical installation p.5
- Before working on the hydraulic system p.5
- Avoid danger p.5
- X safety p.5
- X safety p.6
- Working on cooling systems heat pump p.6
- Site of installation p.6
- Requirements for the heating water p.6
- Operation p.6
- Instructing the user owner p.6
- Heating system and sanitary connection p.6
- X product description p.7
- Top of unit p.7
- Product description p.7
- Design and components p.7
- X product description p.8
- Fig 2 2 design and components of the daikin altherma ehs x h p30a external view and internal design for legend descriptions see tab 2 1 p.8
- Device external and internal design daikin altherma ehs x h p30a p.8
- Device external and internal design daikin altherma ehs x h b p30a p.9
- X product description p.9
- Fig 2 3 design and components of the daikin altherma ehs x h b p30a external view and internal design for legend descriptions see tab 2 1 p.9
- X product description p.10
- Fig 2 4 design and components of the daikin altherma ehs x h p50a external view and internal design for legend descriptions see tab 2 1 p.10
- Device external and internal design daikin altherma ehs x h p50a p.10
- X product description p.11
- Fig 2 5 design and components of the daikin altherma ehs x h b p50a external view and internal design for legend descriptions see tab 2 1 p.11
- Device external and internal design daikin altherma ehs x h b p50a p.11
- X product description p.12
- X set up and installation p.13
- Set up and installation p.13
- Dimensions and connections p.13
- Daikin altherma ehs x h p30a p.13
- Daikin altherma ehs x h p50a p.14
- X set up and installation p.14
- Scope of delivery p.15
- X set up and installation p.15
- Set up p.15
- X set up and installation p.16
- Water connection p.16
- X set up and installation p.17
- Electrical connection p.17
- Connecting hydraulic lines p.17
- X set up and installation p.18
- Overall connection plan daikin altherma ehs x h p.18
- Fig 3 7 overall connection diagram for electrical connection during device installation p.18
- Explanation of symbols and abbreviations in this chap ter see tab 3 2 and tab 3 3 p.18
- The a1p circuit board comes pre connected to the unit no as sembly or connection work is necessary on the a1p circuit board p.19
- Terminal assignment for the rtx ehs circuit board p.19
- Terminal assignment for the rtx al4 circuit board p.19
- Position of the circuit boards p.19
- Connection assignment circuit board a1p p.19
- X set up and installation p.19
- X set up and installation p.20
- Removing the protective cover p.20
- Mains connection daikin altherma ehs x h p.20
- Connection assignment circuit board rocon bm1 p.20
- X set up and installation p.21
- Opening the control housing and establishing electrical connections p.21
- Connection of external temperature sensor rocon ot1 p.21
- Connection of erlq exterior heat pump unit p.21
- X set up and installation p.22
- External demand signal eds p.22
- Connection of an external switching contact p.22
- Connection variant 2 p.23
- Connection variant 1 p.23
- Connection of the electrical daikin backup heater ekbuxx p.23
- Connection of an external heat generator p.23
- X set up and installation p.23
- X set up and installation p.24
- Caution p.24
- X set up and installation p.25
- Daikin room station ehs157034 p.25
- Daikin mixer module ehs157068 p.25
- Connection optional daikin rocon system components p.25
- Connection of the daikin room thermostat p.25
- X set up and installation p.26
- Low tariff mains connection ht nt p.26
- Internet gateway daikin ehs157056 p.26
- Connection switch contacts aux outputs p.26
- Connection of the daikin fwxv 15 20 aveb p.26
- C onnection of the daikin fwxv 15 20 aveb p.26
- Symbols and legend keys on connection and circuit diagrams p.27
- Connection intelligent controller smart grid sg p.27
- X set up and installation p.27
- X set up and installation p.28
- X set up and installation p.29
- Laying coolant lines p.29
- X set up and installation p.30
- Pressure test and filling the coolant circuit p.30
- Filling the system with water p.30
- Filling the storage tank p.30
- Filling the hot water heat exchanger p.30
- Filling the heating system p.30
- Checking the water quality and adjusting the pressure gauge p.30
- Start up p.31
- Set the commissioning parameters p.31
- Requirements p.31
- L commissioning p.31
- Initial commissioning p.31
- X start up p.31
- X start up p.32
- Venting the internal heating circulation pump p.32
- Expert p.32
- X start up p.33
- Start up p.33
- Requirements p.33
- Re commissioning p.33
- Configuring screed program parameters only if necessary p.33
- Check minimum flow p.33
- Activating the parameter air purge p.33
- X start up p.34
- Without solar installation p.35
- Temporary shutdown p.35
- Draining the storage tank p.35
- Decommissioning p.35
- X decommissioning p.35
- X decommissioning p.36
- Only for the solar installation p.36
- Draining the heating circuit and hot water circuit p.36
- X decommissioning p.37
- Recommendations for disposal p.37
- Final shutdown p.37
- X service and maintenance p.38
- Service and maintenance p.38
- Removing the protective cover p.38
- Legal requirements p.38
- General p.38
- Activities to be performed annually p.38
- X service and maintenance p.39
- With kfe filling connection or with installed solar system see also chapter 5 p.40
- Filling and topping up the storage tank p.40
- X service and maintenance p.40
- Without installed solar system p.40
- X service and maintenance p.41
- Filling and topping up the heating system p.41
- X errors malfunctions and messages p.42
- Troubleshooting p.42
- Recognising errors correcting malfunctions p.42
- Read protocol p.42
- Errors malfunctions and messages p.42
- Current fault display p.42
- X errors malfunctions and messages p.43
- Malfunctions p.43
- X errors malfunctions and messages p.44
- X errors malfunctions and messages p.45
- X errors malfunctions and messages p.46
- Fault codes p.47
- X errors malfunctions and messages p.47
- X errors malfunctions and messages p.48
- X errors malfunctions and messages p.49
- X errors malfunctions and messages p.50
- X errors malfunctions and messages p.51
- X errors malfunctions and messages p.52
- Touching live parts can result in an electric shock and lead to potentially fatal injuries and burns p.53
- Pump continuous running off p.53
- No designation factory setting p.53
- Monitoring and configuration dip switch p.53
- Domestic hot water gener ation on p.53
- Do not change off p.53
- Disconnect the system from the power supply open the control housing and remove the rocon bm1 board see chapter 3 check the dip switch setting on the a1p circuit board of the daikin altherma ehs x h adjust where necessary see tab 7 4 the factory preset may only be changed if e g an optional accessory was connected replace the rocon bm1 switch board close the control housing and reconnect the power supply p.53
- Dip switch settings are not recognised until a brief inter ruption to the power supply p.53
- Dip switch p.53
- Before beginning work on live parts disconnect all of the systems circuits from the power supply switch off main switch disconnect fuse and secure against unintentional restart p.53
- X errors malfunctions and messages p.53
- Warning p.53
- X errors malfunctions and messages p.54
- Emergency operation p.54
- X hydraulic system connection p.55
- Hydraulic system connection p.55
- X hydraulic system connection p.56
- X hydraulic system connection p.57
- X technical data p.58
- Technical data p.58
- Equipment data p.58
- Daikin altherma ehs x h p30a p.58
- X technical data p.59
- X technical data p.60
- Daikin altherma ehs x h p50a p.60
- Characteristic lines p.61
- X technical data p.61
- Sensor characteristic lines p.61
- X technical data p.62
- Sensor resistance in ohm p.62
- Sensor output frequency in hz p.62
- Pt 1000 p.62
- Measured temperature in c p.62
- Measured flow in l min p.62
- M l min p.62
- Fls sensor flow temperature p.62
- 14 229 hz p.62
- X technical data p.63
- Tightening torque p.63
- Characteristic curves for pumps p.63
- Fig 9 8 circuit diagram daikin altherma ehs x h for legend see tab 3 3 p.64
- Circuit diagram daikin altherma ehs x h p.64
- X technical data p.64
- X notes p.65
- X notes p.66
- X list of keywords p.67
- Numerics p.67
- List of keywords p.67
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Руководство по применению для установщика
Узнайте, как правильно установить и обслуживать систему отопления и охлаждения. Следуйте инструкциям для безопасной эксплуатации и предотвращения несчастных случаев.