Daikin ERRQ011AAY1 [28/459] Capacity tables

Daikin ERRQ011AAY1 [28/459] Capacity tables
Heating Daikin Altherma
25
Daikin Altherma High Temperature • Outdoor units • ERRQ-AAY1
3 Capacity tables
3 - 1 Heating capacity tables
2
3
3TW58842-1C
ERRQ-AY1
Symbols
HC Heating capacity [kW]
PI Power input [kW]
LW Leaving water temperature
EW Entering water temperature
Peak
Ta[°CDB]
LW [°C] LW [°C] LW [°C] LW [°C] LW [°C]
45 55 65 75 80
[°CDB] HC PI HC PI HC PI HC PI HC PI
Conditions
- nT (Leaving water temperature - Entering water temperature)
- Piping length R410A Refrigerant piping length = 5m
- No pump power input is included
-
if Ta < 3°C and unit has bottom plate heater, 95 W has to be added to PI
value
- Ta < 0°C: RH=75%
- Ta > 0°C: RH=85%
Capacity table
Integrated
Ta[°CDB]
LW [°C] LW [°C] LW [°C] LW [°C] LW [°C]
45 55 65 75 80
[°CDB] HC PI HC PI HC PI HC PI HC PI
flowrate
[l/min]
*011* *014* *016*
nT = 15°C 10,5 13,4 15,3
nT = 10°C 15,8 20,1 22,9
nT = 5°C 31,5 40,1 45,9
101727_BW_EN_004_464_IC.pdf 29 9/06/2010 14:53:32