Daikin ERRQ011AAY1 [39/459] Specifications

Daikin ERSQ016AAY1 [39/459] Specifications
Daikin Altherma High Temperature • Outdoor units • ERSQ-AAV1
Heating Daikin Altherma
36
2 Specifications
3
2
Refrigerant Type R-410A
Charge kg 4.5 4.5 4.5
Control Expansion valve(electronic type)
Nr of Circuits 1 1 1
Refrigerant Oil Type Daphne FVC68D
Charged Volume l 1.5 1.5 1.5
Piping connections Liquid (OD) Quantity 1 1 1
Type Flare connection
Diameter (OD) mm 9,52
Gas Quantity 1 1 1
Type Flare connection
Diameter (OD) mm 15,9
Drain Quantity 3 3 3
Diameter (OD) mm 26x3
Piping Length Minimum m 3 3 3
Maximum m 50 50 50
Equivalent m 63 63 63
Chargeless m 10 10 10
Additional Refrigerant Charge kg/m See installation manual
Installation height
difference
Maximum m 30 30 30
Heat Insulation Both liquid and gas pipes
Defrost Method Reverse cycle
Defrost Control Sensor for outdoor heat exchanger temperature
Capacity Control Method Inverter controlled
Safety Devices High pressure switch
Fan motor thermal protector
Inverter overload protector
PC board fuse
Standard Accessories Item Installation manual
Quantity 1 1 1
High pressure side Design pressure bar 40 40 40
Notes See operation range drawing
2-3 Electrical Specifications ERSQ011AAV1 ERSQ014AAV1 ERSQ016AAV1
Power Supply Name V1
Phase 1~
Frequency Hz 50 50 50
Voltage V 220-440
Voltage range Minimum V 198
Maximum V 254
Current Minimum Ssc value kVa Equipment complying with EN/IEC 61000-S-12 (1)
Maximum running Current
Heating A 23.8 23.8 23.8
Recomended fuses A 25 25 25
Wiring connections For Power Supply Quantity 2G
Remark Select diameter and type according to national and local regulations
For connection with
indoor
Quantity 2 2 2
Remark F1 + F2
Power Supply Intake Both indoor and outdoor unit
Notes (1) European/international technical standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage system with input current > 16A smaller than or equal to 75A
per phase.
In accordance with EN/IEC 61000-3-11 (1), it may be necessary to consult the distribution network
operator to ensure that the equipment is connected only to a supply with Zsys (system impedance)
smaller than or equal to Zmax.
SSC means short-circuit power
(1) European/international technical standard setting the limits for voltage changers, voltage fluctuations
and flicker in public low-voltage supply systems for equipment with rated smaller than or equal to 75A.
2-2 Technical Specifications ERSQ011AAV1 ERSQ014AAV1 ERSQ016AAV1
101727_BW_EN_004_464_IC.pdf 40 9/06/2010 14:53:36