Daikin ERRQ011AAY1 [296/459] Specifications

Daikin ERRQ016AAY1 [296/459] Specifications
Heating Daikin Altherma
293
Daikin Altherma Low Temperature • Monobloc • EBLQ011-016BA6V3
2 Specifications
16
2
Water side Heat
exchanger
Type Brazed plate
Quantity 1 1 1
Water volume l 1.01 1.01 1.01
Water flow rate Min. l/min 16 16 16
Water flow rate
Nom.
Heating l/min 32.1 40.1 45.9
Cooling l/min 28.7 35.8 37.6
Water flow rate Max. l/min 58 58 58
Insulation material Polyurethane foam
Expansion vessel Volume l 10 10 10
Maximum water pressure bar 3 3 3
Pre pressure bar 1.0 1.0 1.0
Water filter Diameter perforations mm 1 1 1
Material Brass
Water circuit Piping connections inch G5/4 (FEMALE)
Piping inch 5/4"
Safety valve bar 3 3 3
Manometer Yes
Drain valve / Fill valve yes
Shut off valve yes
Air purge valve yes
Total water volume (6) l 5.5 5.5 5.5
Minimum water volume system l 20 20 20
2-4 ELECTRICAL SPECIFICATIONS EBLQ011BA6V3 EBLQ014BA6V3 EBLQ016BA6V3
Power supply
compressor
component
Main Power Name V3
Phase 1~ 1~ 1~
Frequency Hz 50 50 50
Voltage V 230 230 230
Voltage range Minimum V -10%
Maximum V +10%
Current Minimum Ssc
value
kVa Equipment complying with EN/IEC 61000-3-12(×)
Current Maximum running
current
Cooling A 26.5 26.5 26.5
Power supply
compressor
component
Current Recomende
d fuses
A32 32 32
Wiring connections For power supply
compressor component
See installation manual
Power supply
hydraulic
component
Current back-up
heater
Type 6V3
Current back-up
heater
Power Supply Phase 1~
Frequency Hz 50 50 50
Voltage V 230 230 230
Running Current Back-up
heater
A26 26 26
Running Current Back-up heater +
booster heater
+EK*V3 A 39(26+13)
Current back-up
heater
Z-max Back-up
heater
A 0.29 0.29 0.29
Back-up
heater +
booster
heater
A 0.17 0.17 0.17
Minimum Ssc value +EK*V3 kVa Equipment complying with EN/IEC 61000-3-12(**)
2-3 MAIN COMPONENTS EBLQ011BA6V3 EBLQ014BA6V3 EBLQ016BA6V3
101727_BW_EN_004_464_IC.pdf 297 9/06/2010 14:55:12