Daikin ERRQ011AAY1 — эффективные внутренние блоки для отопления и горячей воды [91/459]

Daikin ERRQ011AAY1 [91/459] Hydraulic performance
Indoor units • EKHBRD-AAY1
Heating • Daikin Altherma
88
9 Hydraulic performance
9 - 1 Static pressure drop unit
6
9
3TW58849-6
1. The ESP curves are the maximum ESP curves (pump rpm: 4000).
The pump of the indoor module is inverter controlled and controls to
have a fixed _T between return and leaving water temperature.
2. In case of installing a domestic hot water tank there is an additional
pressure drop over the three way valve (delivered as accessory with the
tank)
ESP: External static pressure
Flow: waterflow through the unit
Warning
1. Selecting a flow outside the curves can cause damage to or malfunction
of the unit. See also minimum and maximum allowed water flowrange
in the technical specifications.
2. Water quality must be according to EN directive EC 98/83 EC.
Note:
In case of stand alone tank, available ESP during DHW mode: to be confirmed
EKHBRD011-016AA
unit ESP wit 3way valve
ESP [kPa]
unit ESP without 3way valve
max. ESP if Dt = 10°C
max. ESP if Dt = 5°C
Flow [l/min]
h