43
EN
ATTENTION
If the PLL function is disabled, the automatic by-pass function is also disabled.
Should the variation in input frequency be above the set range, the UPS will inhibit the PLL function and release
the output and input lock. When the range returns within the set threshold, the PLL function will be reinstated
automatically.
ATTENTION!
Programming priority is as follows:
X: either setting (ENABLED or DISABLED)
NB: Load Waiting without mains power.
In “Load Waiting” mode, the UPS will switch the by-pass on when the load is below the set threshold. Should there be no
mains power, the UPS will switch off and only switch on again when mains power is restored.
Bypass Enable
Forced mode
DIP Speed
Off-line mode
Load Wait Mode
By-pass
ð
Bypass Enable
If enabled, the UPS manages by-pass intervention
automatically.
If disabled, the UPS will never switchover to by-pass
operation. The UPS will switch off in cases of lengthy
overload.
Forced mode If enabled, the UPS enters permanent by-pass operation.
DIP Speed
This is to alter the sensitivity of the automatic intervention
by the by-pass (when forced mode is disabled)
SLOW: for loads that are not sensitive to dips in voltage
or micro breaks but that cause frequent peaks.
STANDARD: normal use
FAST: loads sensitive to micro breaks
Off-line mode
If enabled, the by-pass operates as follows:
- When mains power is present, the UPS runs
permanently in by-pass mode
- Should mains power fail, the UPS enters battery mode.
Load Wait Mode
ENABLE: switches the function on or off
If enabled, the by-pass enters operation when the load is
below the threshold set for “Minimum load threshold”
Above this threshold, the by-pass stops working.
Minimum load threshold: to set the value for the load
for the switching on and off function (refer to NB: Load
Waiting without mains power).
Operational
function
Enable
By-pass
Forced
Mode
Off-line
mode
Load
Waiting
FORCED MODE ENABLED ENABLED X X
OFF-LINE MODE ENABLED DISABLED ENABLED ENABLED
OFF-LINE MODE ENABLED DISABLED ENABLED DISABLED
LOAD WAITING MODE ENABLED DISABLED DISABLED ENABLED
AUTOMATIC MODE ENABLED DISABLED DISABLED DISABLED
BY-PASS DISABLED DISABLED X X X