5.7 Battery operation
3 103 38 3 103 39 3 103 40 3 103 41
Approximate autonomy in minutes
with charged batteries
Percentage of applied load 50% 80% 100% 50% 80% 100% 50% 80% 100% 50% 80% 100%
Standard UPS 20 11 8 20 11 8 20 11 8 20 11 8
Recharge time up to 90%
of total charge
5 - 6 hours according to level of discharge
Specifications and quantity
of batteries
n. 3 pcs 12V 9Ah, sealed, lead-acid, maintenance free batteries connected
in series for each power module
Reserve signals from 32.2 V to 36V, can be programmed by operator
Minimum voltage for battery
operation during discharge
from 27V to 31.5V with automatic selection depending on applied load,
or as programmed by operator.
Average battery life
3-6 years according to use and working temperature.
WARNING!
The batteries in the UPS are subject to a reduction in capacity
depending on their age (a feature of lead batteries declared by their
manufacturer in the technical manual). For example, the reduction
of capacity of a 4-year-old battery can be as much as 40%, resulting
in a proportional reduction of UPS autonomy time when running on
battery power.
5.8 By-pass Specifications
3 103 38 3 103 39 3 103 40 3 103 41
Type of by-pass Static and electromechanical
Switchover time zero
5.9 Reference Standards
3 103 38 3 103 39 3 103 40 3 103 41
Safety:
Designed to satisfy standard
Conforms to standard EN 62040-1
Electromagnetic compatibility:
immunity
emission
Conforms to standard EN 62040-2
Typical performance Conforms to standard EN 62040-3
LEGRAND® reserves the right to vary data and specifications without notice.