Legrand MegaLine Rack 2500 [45/132] Megaline rack

Legrand MegaLine Rack 2500 [45/132] Megaline rack
Megaline Rack
45
EN
Set capacity
Battery Thresholds
SIMPLE MODE
Batteries
ð
Set capacity Simple mode
Battery
Thresholds
Sets the warning signal for the end of battery
autonomy using the battery voltage.
There are two possible settings in the
Mode menu
If you select
Mode – Automatic thresholds
The UPS automatically calculates the voltage
thresholds based on the load: the UPS will signal
AUTONOMY RESERVE and END OF AUTONOMY,
respectively, below these.
If you select
Mode – Fixed thresholds
There are two options for this setting:
1) Reserve threshold
Sets the battery voltage threshold; the UPS will signal
AUTONOMY RESERVE below this
2) Exhaust threshold.
Sets the battery voltage threshold; the UPS will signal
END OF AUTONOMY below this.
Max Time On Batt.
Max time reserve
TurnOn Test Enable
Restart Enable
External options
Batteries
ð
Max Time
On Batt.
Sets the maximum time for continuous operation
in BATTERY mode, shown in seconds.
If “0” is set, this function is disabled.
Max time
reserve
Sets the maximum time for operation in BATTERY
mode after the reserve limit has been reached,
shown in seconds. If “0” is set, this function is disabled.
TurnOn Test
Enable
If enabled, the batteries are tested each time
the UPS is switched on. If disabled, the batteries
are not tested when it is switched on again.
Restart
Enable
If enabled, the UPS will switch on again when mains
power is restored after switching off due to the end of its
autonomy. If disabled, the UPS will not switch back on
when mains power is restored after switching off due to
the end of its autonomy.
External
options
Battery Chargers N°
Sets the number of external battery chargers
KB Units
Sets the number of packs of three batteries fitted
externally