Moxa ioLogik E1210 [15/115] Inputs and outputs

Moxa ioLogik E1240 [15/115] Inputs and outputs
ioLogik E1200 Series Introduction
1-11
ioLogik E1262
Inputs and Outputs
Thermocouples:
8 channels
Isolation:
3k VDC or 2k Vrms
Thermocouple
Sensor Type:
J (0 to 750°C), K (-200 to 1250°C), T (-200 to 350°C),
E (
-200 to 900°C), R (-50 to 1600°C), S (-50 to 1760°C), B (600 to 1700°C), N (-200 to 1300°C)
Millivolt Type:
• Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV
• Fault and over
-voltage protection:
-35 to +35 VDC (power off)
-25 to +30 VDC (power on)
Sampling Rate:
• All channels: 12 samples/sec
• Per channel: 1.5 samples/sec
• Only one channel enabled: 12
samples/sec
Resolution:
16 bits
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @
-40 and 75°C
Input Impedance:
10 mega-ohms
Power Requirements
Input Voltage:
12 to 36 VDC
Input Current:
118 mA @ 24 VDC
MTBF (mean time between failures)
Time:
631,418 hrs.
Standard:
Telcordia SR332

Содержание