Mitsubishi Electric PUHY-RP200YJM-A Инструкция по установке онлайн [4/34] 278261

Mitsubishi Electric PUHY-RP200YJM-A Инструкция по установке онлайн [4/34] 278261
4
A (mm)
Å Outdoor model
RP200
RP250
RP300
RP350
RP400
RP450
RP500
RP550
RP600
RP650
RP700
RP750
RP800
RP850
RP900
unit1
-
-
-
-
RP200
RP200
RP250
RP250
RP300
RP300
RP200
RP250
RP250
RP250
RP300
unit2
-
-
-
-
RP200
RP250
RP250
RP300
RP300
RP350
RP250
RP250
RP250
RP300
RP300
unit3
-
-
-
-
-
-
-
-
-
-
RP250
RP250
RP300
RP300
RP300
ı Liquid pipe
ø12.7
ø12.7
ø12.7
ø15.88
ø15.88
ø15.88
ø15.88
ø15.88
ø19.05
ø19.05
ø19.05
ø19.05
ø19.05
ø19.05
ø19.05
Ç Gas pipe
ø28.58*2
ø28.58
ø28.58
ø34.93
ø34.93
ø34.93
ø34.93
ø34.93
ø34.93
ø41.28
ø41.28
ø41.28
ø41.28
ø41.28
ø41.28
ı Liquid pipe
-
-
-
-
ø9.52
ø9.52
ø9.52
ø9.52
ø12.7
ø12.7
ø9.52
ø9.52
ø9.52
ø9.52
ø12.7
Ç Gas pipe
-
-
-
-
ø19.05
ø19.05
ø22.2
ø22.2
ø22.2
ø22.2
ø19.05
ø22.2
ø22.2
ø22.2
ø22.2
ı Liquid pipe
-
-
-
-
ø9.52
ø9.52
ø9.52
ø12.7
ø12.7
ø12.7
ø9.52
ø9.52
ø9.52
ø12.7
ø12.7
Ç Gas pipe
-
-
-
-
ø19.05
ø22.2
ø22.2
ø22.2
ø22.2
ø28.58
ø22.2
ø22.2
ø22.2
ø22.2
ø22.2
ı Liquid pipe
-
-
-
-
-
-
-
-
-
-
ø9.52
ø9.52
ø12.7
ø12.7
ø12.7
Ç Gas pipe
-
-
-
-
-
-
-
-
-
-
ø22.2
ø22.2
ø22.2
ø22.2
ø22.2
ı Liquid pipe
-
-
-
-
-
-
-
-
-
-
ø19.05
ø19.05
ø19.05
ø19.05
ø19.05
Ç Gas pipe
-
-
-
-
-
-
-
-
-
-
ø34.93
ø34.93
ø34.93
ø34.93
ø34.93
Unit combination A A1 *1 A2 *1 A3 *1 A4
9.2
9
*1 The pipe sizes listed in columns A1 to A3 in this table correspond to the
sizes for the models listed in the unit 1, 2, and 3 columns. When the order
of the models for unit 1, 2, and 3 change, make sure to use the appropriate
pipe size.
*2 ø25.4 for R22
B, C, D (mm)
a, b, c, d, e (mm)
Ï Downstream unit model total
~ 200
201 ~ 400
401 ~ 650
Ó The 1st branch of P450 ~ P650
651 ~
È
The 1st branch of P700, P750, P800
Ì Joint
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2
Î Total capacity of indoor units
~ 80
81 ~ 160
161 ~ 330
331 ~ 480
481 ~ 630
631 ~
ı Liquid pipe
ø9.52
ø12.7
ø12.7
ø15.88
ø15.88
ø19.05
Ç Gas pipe
ø15.88
ø19.05
ø25.4 or ø28.58
ø31.75 or ø34.93
ø38.1 or ø34.93
ø41.28
Model number
15,20,25,32,40
50,63,71,80
100,125,140
200,250
ı Liquid pipe
ø6.35
ø9.52
ø9.52
ø12.7
Ç Gas pipe
ø12.7
ø15.88
ø19.05
ø28.58
Ô 4-Branching header
(Downstream unit
model total
=
200)
CMY-Y104-G
8-Branching header
(Downstream unit
model total
=
400)
CMY-Y108-G
Ò
10-Branching header
(Downstream unit
model total
=
650)
CMY-Y1010-G
Å Outdoor model
P400 ~ P650
P700 ~ P900
˜
Outdoor twinning kit
CMY-RP100VBK
CMY-RP200VBK

Содержание