(1) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working temperature
in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
SSWWSS//SSWWRR RR113344aa 11660022 11990022 22220022 22221122 22335522
Nominal voltage V(%)-ph-Hz 400 ±10% / 3 / 50
Nominal power input kW 78.8 95 114.4 158 166
Max power input kW 109.6 132.4 159.4 220 230
Nominal current A 141 169 204 266 279
Max. current (FLA) A 192 210 260 360 395
Max. start-up current (LRA) A 347.2 424.5 586 393 417.5
External fuses (A) 250 250 315 400 400
Wire cross area (1)
(*) mm
2
120 120 185 2x150 2x150
CCoommpprreessssoorrss
Number 22222
Nominal power input kW 2x39.4 2x47.5 2x57.2 2x79 79+87
Max power input kW 2x54.8 2x66.2 2x79.7 2x110 110+120
Nominal current A 2x70 2x85 2x102 2x133 133+146
Max. current (FLA) A 2x96 2x105 2x130 2x180 180+215
Max. start-up current (LRA) A 2x280 2x351 2x495 2x267 267+314
Oil treater power input W 200 200 200 300 300
SSWWSS//SSWWRR RR113344aa 22550022 22665522 22880022 33001122 33220022
Nominal voltage V(%)-ph-Hz 400 ±10% / 3 / 50
Nominal power input kW 174 184 194 211 228
Max power input kW 240 251 262 286 310
Nominal current A 292 310 328 351 374
Max. current (FLA) A 430 446 462 511 560
Max. start-up current (LRA) A 464.5 491.5 502.7 597.7 632
External fuses (A) 500 500 500 630 630
Wire cross area (1)
(*) mm
2
2x150 2x185 2x150 2x185 2x185
CCoommpprreessssoorrss
Number 22222
Nominal power input kW 2x87 87+97 2x97 97+114 2x114
Max power input kW 2x120 120+131 2x131 131+155 2x155
Nominal current A 2x146 146+164 2x164 164+187 2x187
Max. current (FLA) A 2x215 215+231 2x231 231+280 2x280
Max. start-up current (LRA) A 2x280 314+341 2x341 341+436 2x436
Oil treater power input W 300 300 300 300 300