Airwell SWS 2652 HFС 134a [28/82] English

Airwell SWS 2652 HFС 134a [28/82] English
Page 27
English
General Description
7.4 Refrigerant circuits
Every single SWS unit has two complete refrigerant
circuits, one per compressor. Each refrigerant circuit
includes: a service valve for refrigerant filling, shutoff
valves for suction lines (on request), as well as for the
delivery and liquid lines, a thermostatic expansion
valve with external equalizer, a solenoid valve to
start/stop the compressor, a dehydrating cartridge
filter, a sight glass with humidity indicator, a differen-
tial oil pressure switch. The moto-evaporating SWR
units, which derive from the SWS versions, are
marked by the absence of condensers, are provided
with shutoff cocks on the delivery and liquid lines, so
as to allow the connection of remote condensers.
Each circuit is also provided with safety devices, in
accordance with PED 97/23/EC: HP pressure
switches, pressure transducers, safety valves provid-
ing protection in case of fire or in the case of a mal-
function of compressors.
7.5 Evaporator
All units are equipped with a single direct-expansion
refrigerant/water exchanger of shell and tube type,
with several refrigeration circuits. The tube bundle
can be removed for any inspections or maintenance.
The heat exchangers are insulated with 19mm-thick
anti-condensate closed-cell polyethylene material.
The insulating material is not UV-ray-proof.
7.6 Condenser
All units are provided with two condensers (one per
circuit). The heat exchanger is of shell and tube type,
with square plates, preset for opening for inspection,
cleaning and maintenance purposes.
SWS refrigeration diagram
9 Sight glass
10 Thermostatic valve
11 Evaporator
12 Safety valve
13 Suction cock (optional)
14 Nonreturn valve (optional)
15 Solenoid valve (optional)
16 Capillary (optional)
Components:
1 Screw compressor
2 Screw compressor’s
delivery cock
3 Flexible hose - absorber
(ELN version only)
4 Silencer (ELN version only)
5 Condenser
6 Safety valve
7 Liquid cock
8 Filter
Safety devices:
A HP pressure switch
B LP pressure switch
C Transducer
D Differential water pressure switch
Filling/discharge and
pressure/intakes Freon
Note: the units are equipped with two re-
frigeration circuits. Only one circuit is
illustrated for the sake of simplicity.