TTeecchhnniiccaall ddaattaa
SSWWSS//SSWWRR RR113344aa 33441122 33660022 44221122 44660022 44880022
Nominal voltage V(%)-ph-Hz 400 ±10% / 3 / 50
Nominal power input kW 249 270 298 315 322
Max power input kW 359 408 408 426 444
Nominal current A 404 434 492 519 546
Max. current (FLA) A 590 620 620 670 720
Max. start-up current (LRA) A 661 682 803 867 902
External fuses (A) 630 630 630 800 800
Wire cross area (1)
(*) mm
2
2x185 2x185 2x185 2x240 2x240
CCoommpprreessssoorrss
Number 22222
Nominal power input kW 114+135 2x135 2x149 149+166 2x166
Max power input kW 155+204 2x204 2x204 204+222 2x222
Nominal current A 187+217 2x217 2x246 246+273 2x273
Max. current (FLA) A 280+310 2x310 2x310 310+360 2x360
Max. start-up current (LRA) A 436+465 2x465 2x586 586+650 2x650
Oil treater power input W 300 300 300 300 300
(1) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum working temperature
in the room, the type of insulation and the cable laying, the maximum length of the power supply line.