ABB AS09-30-10-26 [174/202] Draf09 draf16 enclosed direct on line starters up to 7 kw and 10 hp protected by thermal overload relays ac operated

ABB ASL09-30-10-81 [174/202] Draf09 draf16 enclosed direct on line starters up to 7 kw and 10 hp protected by thermal overload relays ac operated
1SBC133006S0201
7/6 | ABB Motor protection and control - short form catalog
DRAF09 … DRAF16 enclosed direct-on-line starters
Up to 7.5 kW and 10 hp, protected by thermal overload relays
AC operated
Description
Enclosed direct-on-line (DOL) starters are used for controlling 3-phase asynchronous motors up to 690 V AC.
Each starter is delivered assembled and wired. It contains:
IP66 and type 4X plastic enclosure with double insulation, equiped with:
- 1 green flush "I" ON button and 1 red protruding "O" OFF/RESET button
- 4 cable inlets and outlets via knockouts.
1 AF 3-pole contactor with holding contact
1 CB5-10 start contact block
1 PE and 1 neutral terminal.
Control supply wiring:
IEC starters type: phase-to-phase, separate supply or phase-to-neutral.
UL starters type: separate supply.
TF42 thermal overload relay to be ordered separately and choses according to motor's nominal current (see
table in the next page).
DRAF enclosed DOL starters
IEC - AC-3 Control supply
wiring
Rated control
circuit
voltage
Uc min ... Uc max
(1)
Type Order code Weight
Pkg
(1 pce)
Rated operational
power max.
current
θ ≤ 40°C
Ue=400 V
220V
230V
240V
380 V
400V
500V 690V
kW kW kW kW A V 50/60Hz kg
IEC starters type
2.2 4 5.5 5.5 9 Separate supply 24…60 DRAF09-11S 1SBK134237R1100 0.820
Phase-to-neutral 100...250 DRAF09-13N 1SBK134137R1300 0.820
Phase-to-phase 250...500 DRAF09-14P 1SBK134037R1400 0.820
3 5.5 7.5 7.5 12 Separate supply 24…60 DRAF12-11S 1SBK154237R1100 0.820
Phase-to-neutral 100...250 DRAF12-13N 1SBK154137R1300 0.820
Phase-to-phase 250...500 DRAF12-14P 1SBK154037R1400 0.820
4 7.5 9 9 18 Separate supply 24…60 DRAF16-11S 1SBK174237R1100 0.820
Phase-to-neutral 100...250 DRAF16-13N 1SBK174137R1300 0.820
Phase-to-phase 250...500 DRAF16-14P 1SBK174037R1400 0.820
(1) Select DRAF..S with separate supply for 24...60 V DC control circuit voltage (change A2 - Us wire to blue color acc. to IEC 60947-4-1).
UL starter type with separate control supply wiring
UL / CSA Rated control
circuit
voltage
Uc min ... Uc max
Type Order code Weight
Pkg
(1 pce)
Horse power ratings
Single phase motor Three phase motor
120V 240 V 200V
208 V
220V
240 V
440V
480 V
550V
600 V
hp hp hp hp hp hp V 50/60Hz kg
UL starters type
0.75 1.5 2 2 5 7.5 24…60 DRAF09-11U 1SBK134238R1100 0.820
100...250 DRAF09-13U 1SBK134238R1300 0.820
250...500 DRAF09-14U 1SBK134238R1400 0.820
1 2 3 3 7.5 10 24…60 DRAF12-11U 1SBK154238R1100 0.820
100...250 DRAF12-13U 1SBK154238R1300 0.820
250...500 DRAF12-14U 1SBK154238R1400 0.820
1.5 3 5 5 10 15 24…60 DRAF16-11U 1SBK174238R1100 0.820
100...250 DRAF16-13U 1SBK174238R1300 0.820
250...500 DRAF16-14U 1SBK174238R1400 0.820
DRAF
+ TF42 to be ordered separately
1SBC133005V0014
7
Time) Time) Time)

Содержание

Скачать