ABB AS09-30-10-26 [87/202] Dol starters protected by ms manual motor starters coordination type 2

ABB ASL09-30-10-81 [87/202] Dol starters protected by ms manual motor starters coordination type 2
ABB Motor protection and control - short form catalog | 5/11
Coordination type 2, AC-3, 16 kA or 50 kA, 400 V, 50/60 Hz
Manual motor starters Contactors Accessories
I >
CA4-10BEA..-4
IEC
Type
(1)
Order code Current
setting
range
Mag
netic
tripping
current
Rated control circuit
voltage
Uc min. ... Uc max.
(2)
Type
(3)
Order code Allowed
setting
current
Type
(4)
Order code
AC-3, 400 V
Rated
operational
power
current
kW A
A A
V 50/60 Hz
V DC A
0.06 0.2 MS132-0.25 1SAM350000R1002 0.16...0.25 2.44 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.25 BEA16-4 1SBN081306T1000
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.09 0.3 MS132-0.4 1SAM350000R1003 0.25...0.40 3.9 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.4
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.12 0.44 MS132-0.63 1SAM350000R1004 0.40...0.63 6.14 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.63
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.18 0.6 MS132-0.63 1SAM350000R1004 0.40...0.63 6.14 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 0.63
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.25 0.85 MS132-1.0 1SAM350000R1005 0.63...1.00 11.5 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.37 1.1 MS132-1.6 1SAM350000R1006 1.00...1.60 18.4 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1.6
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.55 1.5 MS132-1.6 1SAM350000R1006 1.00...1.60 18.4 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 1.6
100...250 100...250 AF09-30-10-13 1SBL137001R1310
0.75 1.9 MS132-2.5 1SAM350000R1007 1.60...2.50 28.75 24...60 20...60 AF09Z-30-10-21 1SBL136001R2110 2.5
100...250 100...250 AF09-30-10-13 1SBL137001R1310
1.1 2.7 MS132-4.0 1SAM350000R1008 2.50...4.00 50 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 4
+
BEA26-4
CA4-10
1SBN082306T1000
1SBN010110R1010
100...250 100...250 AF26-30-00-13 1SBL237001R1300
1.5 3.6 MS132-4.0 1SAM350000R1008 2.50...4.00 50 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 4
100...250 100...250 AF26-30-00-13 1SBL237001R1300
2.2 4.9 MS132-6.3 1SAM350000R1009 4.00...6.30 78.75 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 6.3
100...250 100...250 AF26-30-00-13 1SBL237001R1300
3 6.5 MS132-10 1SAM350000R1010 6.30...10.0 150 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 10
100...250 100...250 AF26-30-00-13 1SBL237001R1300
4 8.5 MS132-10 1SAM350000R1010 6.30...10.0 150 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 10
100...250 100...250 AF26-30-00-13 1SBL237001R1300
5.5 11.5 MS132-12 1SAM350000R1012 8.00...12.0 180 24...60 20...60 AF26Z-30-00-21 1SBL236001R2100 12
+
BEA38-4
CA4-10
1SBN082306T2000
1SBN010110R1010
100...250 100...250 AF26-30-00-13 1SBL237001R1300
7.5 15.5 MS132-16 1SAM350000R1011 10.0...16.0 240 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 16
100...250 100...250 AF30-30-00-13 1SBL277001R1300
11 22 MS132-25 1SAM350000R1014 20.0...25.0 375 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 25
100...250 100...250 AF30-30-00-13 1SBL277001R1300
15 29 MS132-32 1SAM350000R1015 25.0...32.0 480 24...60 20...60 AF30Z-30-00-21 1SBL276001R2100 32
100...250 100...250 AF30-30-00-13 1SBL277001R1300
18.5 35 MS165-42 1SAM451000R1015 30.0…42.0 630 24…60 20…60 AF40-30-00-11 1SBL347001R1100 40 BEA65-4
CA4-10
1SBN083406R1000
1SBN010110R1010
100...250 100...250 AF40-30-00-13 1SBL347001R1300
22 41 MS165-54 1SAM451000R1016 40.0…54.0 810 24…60 20…60 AF52-30-00-11 1SBL367001R1100 53
100...250 100...250 AF52-30-00-13 1SBL367001R1300
30 55 MS165-65 1SAM451000R1017 52.0…65.0 975 24…60 20…60 AF65-30-00-11 1SBL387001R1100 65
100...250 100...250 AF65-30-00-13 1SBL387001R1300
37 66 MS495-75 1SAM550000R1008 57.0…75.0 975 24…60 20…60 AF80-30-00-11 1SBL397001R1100 75
100…250 100…250 AF80-30-00-13 1SBL397001R1300
45 80 MS495-90 1SAM550000R1009 70.0…90.0 1170 24…60 20…60 AF96-30-00-11 1SBL407001R1100 90
100…250 100…250 AF96-30-00-13 1SBL407001R1300
(1) MS116 manual motor starter can be selected according to the current setting range indicated on the coordination line, up to
- 15 kW 400V - AC-3 at 16 kA
- 4 kW, 400 V - AC-3 at 50 kA.
(2) For other control voltages, see "Voltage code table".
(3) AF26 3-pole contactor can be selected for coordination type 2, 16 kA, 7.5 kW, 400 V - AC-3.
AF38 3-pole contactor can be selected for coordination type 2, 16 kA and 50 kA, 18.5 kW, 400 V - AC-3 (BEA65-4 available for AF40 ... AF65 only).
(4) BEA26-4 should be selected with MS116-12 … MS116-16 and AF26 … AF38.
BEA38-4 can only be selected with MS116-20 … MS116-32.
DOL starters protected by MS manual motor starters
Coordination type 2
1SBC101914S0201 - Rev. C
5
Time) Time) Time)

Содержание