Danfoss VLT AQUA Drive FC-202P3K0S2 [27/40] Start stop two pole motor oversynchronous motor thermistor 0 72 hz reference value via terminal 53 motor thermistor monitoring on terminal 19 visual alarm indication

Danfoss VLT AQUA Drive FC-202P45KT2 [27/40] Start stop two pole motor oversynchronous motor thermistor 0 72 hz reference value via terminal 53 motor thermistor monitoring on terminal 19 visual alarm indication
6
This example constitutes a non-binding recommendation with regard
to the General Delivery and Warranty Conditions. It is based on the
factory setup and presumes that the motor data has been confi gured
correctly. This recommendation must be veri ed by the user.
6.4 Start/stop, two-pole motor, oversynchronous, motor thermistor
0–72 Hz reference value via terminal 53.
Motor thermistor monitoring on terminal 19.
Visual alarm indication.
Start/Stop
Motor thermistor
Analogue reference
Alarm
Motor running
Relevant parameters
Par. Function Setting
0-02 Hz/rpm selection [1] Hz
1-25 Rated motor speed see motor nameplate
5-10 Terminal 18: digital input [8] Start*
5-11 Terminal 19: digital input [0] Not used
5-12 Terminal 27: digital input [0] Not used
1-90 Motor thermal protection [2] Thermistor trip
1-93 Thermistor connection [4] Digital input 19
3-03 Max. reference 72 Hz
3-15 Variable reference 1 [1] Analogue input 53*
4-14 Max. frequency [Hz] 72 Hz
4-53 High speed warning 4320 rpm
6-15 Ter. 53 scale max. ref/feedback 72 Hz
5-40 [0] Relay 1 function [9] Alarm
5-40 [1] Relay 2 function [5] Motor running
* Factory setting
*Safe stop as option
Relay 2
Relay 1