Chapter 10 Summary of Parameter Settings|C200 Series
10-25
08 High-function PID Parameters
Parameter Explanation Settings
Factory
Setting
08-00
Input Terminal for PID
Feedback
0: No function
1: Negative PID feedback: input from external terminal
AVI (Pr.03-00)
2: Negative PID feedback from PG card (Pr.10-15, skip
direction)
3: Negative PID feedback from PG card (Pr.10-15)
4: Positive PID feedback from external terminal AVI
(Pr.03-00)
5: Positive PID feedback from PG card (Pr.10-15, skip
direction)
6: Positive PID feedback from PG card (Pr.10-15)
0
08-01 Proportional Gain (P) 0.0~500.0% 1.0
08-02 Integral Time (I) 0.00~100.00sec 1.00
08-03 Derivative Control (D) 0.00~1.00sec 0.00
08-04
Upper Limit of Integral
Control
0.0~100.0% 100.0
08-05
PID Output Frequency
Limit
0.0~110.0% 100.0
08-06 Reserved
08-07 PID Delay Time
0.0~2.5
0.0
08-08
Feedback Signal
Detection Time
0.0~3600.0sec 0.0
08-09
Feedback Signal Fault
Treatment
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
0
08-10 Sleep Frequency
Pr.08-18=0: 0.00 ~ 600.00Hz
Pr.08-18=1: 0.00~200.00%
0.00
08-11 Wake-up Frequency
Pr.08-18=0: 0.00 ~ 600.00Hz
Pr.08-18=1: 0.00~200.00%
0.00
08-12 Sleep Time 0.0 ~ 6000.0sec 0.0
08-13 PID Deviation Level 1.0 ~ 50.0% 10.0
08-14 PID Deviation Time 0.1~300.0sec 5.0
08-15
Filter Time for PID
Feedback
0.1~300.0sec 5.0
08-16
PID Compensation
Selection
0: Parameter setting
1: Reserved
0
08-17 PID Compensation -100.0~+100.0% 0
08-18
Setting of Sleep Mode
Function
0: Follow PID output command
1: Follow PID feedback signal
0
08-19 Wake-up Integral Limit 0.0~200.0% 50.0
08-20 PID Mode Selection
0: Serial connection
1: Parallel connection
0
08-21
Enable PID to Change
Operation Direction
0: Operation direction can be changed
1: Operation direction can not be changed
0