Daikin Microtech III [14/44] The circuit mode set points cannot be changeable unless the corresponding circuit switch is off the compressor enable set points cannot not be changeable unless the corresponding compressor is not running

Daikin Microtech III [14/44] The circuit mode set points cannot be changeable unless the corresponding circuit switch is off the compressor enable set points cannot not be changeable unless the corresponding compressor is not running
- 14 -
Condenser Target 67% 33.0°C (91.4°F) 25 to 55 °C (77 to 131 °F)
Condenser Target 50% 30.0°C (86°F) 25 to 55 °C (77 to 131 °F)
Condenser Target 33% 30.0°C (86°F) 25 to 55 °C (77 to 131 °F)
VFD Max Speed 100% 60 to 110%
VFD Min Speed 25% 25 to 60%
Fan Stage Up Deadband 1 8.33°C (15°F) 0 to 15 °C (0 to 27 °F)
Fan Stage Up Deadband 2 5.56°C (10°F) 0 to 15 °C (0 to 27 °F)
Fan Stage Up Deadband 3 5.56°C (10°F) 0 to 15 °C (0 to 27 °F)
Fan Stage Up Deadband 4 5.56°C (10°F) 0 to 15 °C (0 to 27 °F)
Fan Stage Down Deadband 1 11.11°C (20°F) 0 to 15 °C (0 to 27 °F)
Fan Stage Down Deadband 2 11.11°C (20°F) 0 to 15 °C (0 to 27 °F)
Fan Stage Down Deadband 3 8.33 °C (15 °F) 0 to 15 °C (0 to 27 °F)
Fan Stage Down Deadband 4 5.56 °C (10 °F) 0 to 15 °C (0 to 27 °F)
Sensor Offsets
Evap pressure offset 0 kPa (0 psi) -100 to 100 kPa (-14.5 to 14.5 psi)
Cond pressure offset 0 kPa (0 psi) -100 to 100 kPa (-14.5 to 14.5 psi)
Suction temp offset 0°C (0°F) -5.0 to 5.0 °C (-9.0 to 9.0 °F)
Note – Condenser Target 67% and Condenser Target 33% will be available only when number of Comps is 3 (1
circuit) or 6 (2 circuits). Condenser Target 50% will be available only when Number of Compressors is 2 (1 circuit)
or 4 (2 circuits).
6.1.1. Auto Adjusted Ranges
Some settings have different ranges of adjustment based on other settings:
Cool LWT 1, Cool LWT 2, and Network Cool Set Point
Available Mode Selection Range
Without Glycol 4.0 to 15.0 °C (39.2 to 59.0 °F)
With Glycol -15.0 to 15.0 °C (5 to 59.0 °F)
Evaporator Water Freeze
Available Mode Selection Range
Without Glycol 2.0 to 5.6 °C (35.6 to 42 °F)
With Glycol -17.0
(*)
to 5.6 °C (1.4 to 42 °F)
Low Evaporator Pressure Hold and Unload
Available Mode Selection Range
Without Glycol 669 to 793 kPa (97 to 115 psi)
With Glycol 300 to 793 kPa (43.5 to 115 psi)
Low Ambient Lockout
Fan VFD Range
= no for all circuits -18.0 to 15.6 °C (-0.4 to 60 °F)
= yes on any circuit -23.3 to 15.6 °C (-9.9 to 60 °F)
(*) Proper amount of antifreeze must be applied
6.1.2. Special Set Point Operations
The following set points cannot be changeable unless the unit switch is off:
Number of Circuits
Number of Compressors
Number of Fans
Fan VFD enable
LLS Valve enable
Double Stpt enable
LWT Reset enable
Demand Lim enable
Ext Alarm enable
The Circuit Mode set points cannot be changeable unless the corresponding circuit switch is off.
The Compressor Enable set points cannot not be changeable unless the corresponding compressor is not running.
EXV Position set point on each circuit follows the actual EXV position while EXV Control = Auto. When EXV
Control = Manual, the position set point is changeable.