5. Controller Inputs and Outputs
5.1. Main Controller
5.1.1. Analog Inputs
Description
Signal Type
Expected Range
AI1 Evaporator EWT NTC Thermister (10K@25°C) -50°C – 120°C
AI2 Evaporator LWT NTC Thermister (10K@25°C)
-50°C – 120°C
AI3 Outside Ambient Temperature NTC Thermister (10K@25°C)
-50°C – 120°C
X1 Circuit #1 Evaporator Pressure Ratiometric (0,5-4,5 Vdc)
0 to 5 Vdc
X2 Circuit #1 Condenser Pressure Ratiometric (0,5-4,5 Vdc) 0 to 5 Vdc
X3 Circuit #1 Suction Temperature NTC Thermister (10K@25°C)
-50°C – 120°C
X4 Freeze Temperature NTC Thermister (10K@25°C)
-50°C – 120°C
X5 Circuit #2 Evaporator Pressure Ratiometric (0,5-4,5 Vdc)
0 to 5 Vdc
X6 Circuit #2 Condenser Pressure Ratiometric (0,5-4,5 Vdc) 0 to 5 Vdc
X7 Circuit #2 Suction Temperature NTC Thermister (10K@25°C) -50°C – 120°C
5.1.2. Analog Outputs
None
5.1.3. Digital Inputs
Description
Signal Off
Signal On
DI1 PVM Fault On Fault Off
DI2 Evaporator Flow Switch Fault On Fault Off
DI3 Circuit #1 Switch Circuit #1 Disabled Circuit #1 Enabled
DI4 Circuit #2 Switch Circuit #2 Disabled Circuit #2 Enabled
DI5 Unit Switch Unit Disabled Unit Enabled
5.1.4. Digital Outputs
Description
Output Off
DO1 Circuit #1 Compressor 1 C#1 Comp#1 Off C#1 Comp#1 On
DO2 Circuit #1 Compressor 2 C#1 Comp#2 Off C#1 Comp#2 On
DO3 Circuit #2 Compressor 1 C#2 Comp#1 Off C#2 Comp#1 On
DO4 Circuit #2 Compressor 2 C#2 Comp#2 Off C#2 Comp#2 On
DO5 Circuit #1 Fan Output 1 C#1 Stage 1 Fan(s) Off C#1 Stage 1 Fan(s) On
DO6 Circuit #1 Fan Output 2 C#1 Stage 2 Fan(s) Off C#1 Stage 2 Fan(s) On
DO7 Circuit #1 Fan Output 3 C#1 Stage 3 Fan(s) Off C#1 Stage 3 Fan(s) On
DO8 Circuit #2 Fan Output 1 C#2 Stage 1 Fan(s) Off C#2 Stage 1 Fan(s) On
DO9 Circuit #2 Fan Output 2 C#2 Stage 2 Fan(s) Off C#2 Stage 2 Fan(s) On
DO10 Circuit #2 Fan Output 3 C#2 Stage 3 Fan(s) Off C#2 Stage 3 Fan(s) On
5.2. Options expansion module
5.2.1. Analog Inputs
Description
Signal Type
Expected Range
X3 Demand Limit Current Output (0-20 mA) 0-20 mA
X7 LWT Reset Current Output (0-20 mA)
0-20 mA
5.2.2. Analog Outputs
Description
Signal Type
Range
X5 Circuit 1 Fan VFD Voltage Output (0-10 Vdc) 0-100%
X6 Circuit 2 Fan VFD Voltage Output (0-10 Vdc) 0-100%
5.2.3. Digital Inputs
Description
Signal Off
Signal On
DI1 Double Set point Double Set point disable Double Set point enable