Daikin Microtech III — процедуры насосного отключения и низкотемпературного запуска [26/44]

- 26 -
T3 – Run to Pumpdown
Any of the following are required:
Last compressor on circuit is commanded to stop
Unit State = Pumpdown
Circuit switch is open
Circuit mode is disable
Circuit Pumpdown alarm is active
T4 – Pumpdown to Off
Any of the following are required:
Evaporator Pressure < Pumpdown Pressure Value
Unit State = Off
Circuit Rapid Stop alarm is active
T5 – Run to Off
Any of the following are required:
Unit State = Off
Circuit Rapid Stop alarm is active
A low ambient start attempt failed
T6 – Preopen to Off
Any of the following are required:
Unit State = Off
Unit State = Pumpdown
Circuit switch is open
Circuit mode is disable
Circuit Rapid Stop alarm is active
Circuit Pumpdown alarm is active
9.3. Pumpdown Procedure
The pumpdown is performed as follows:
If multiple compressors are running, shut off the appropriate compressors based on sequencing logic and leave
only one running
Turn off liquid line output (if present)
Keep running until evaporator pressure reaches the pumpdown pressure, then stop compressor
If evaporator pressure does not reach pumpdown pressure within two minutes, stop compressor
9.4. Low Ambient Starts
A low OAT start is initiated if the condenser refrigerant saturated temperature is less than 29.5°C (85.1° F) when the
first compressor starts. Once the compressor starts the circuit is in a low OAT start state for a time equal to the Low
OAT Start Time set point. During Low OAT Starts, the freezestat logic for the low evaporator pressure alarm as
well as the low evaporator pressure hold and unload alarms are disabled. The absolute limit for low evaporator
pressure is enforced and the low evaporator pressure alarm is triggered if the evaporator pressure drops below that
limit.
When the Low OAT Start Timer has expired, if the evaporator pressure is greater than or equal to the Low
Evaporator Pressure Unload set point, the start is considered successful and normal alarm and event logic is
reinstated. If the evaporator pressure is less than the Low Evaporator Pressure Unload set point when the Low OAT
Start Timer expires, the start is unsuccessful and the compressor will shut down.
Multiple Low Ambient Start attempts are allowed. On the third failed Low Ambient Start attempt the Restart Alarm
is triggered and the circuit will not attempt to restart until the Restart alarm has been cleared.
The restart counter is reset when either a startup is successful, the Low OAT Restart alarm is triggered, or the unit
time clock shows that a new day has started.