10.1.2. Evaporator Flow Loss
Trigger:
1: Evaporator Pump State = Run AND Evaporator Flow Digital Input = No Flow for time > Flow Proof Set Point
AND at least one compressor running
2: Evaporator Pump State = Start for time greater than Recirc Timeout Set Point and all pumps have been tried and
Evaporator Flow Digital Input = No Flow
Action Taken: Rapid stop all circuits
Reset:
This alarm can be cleared at any time manually via the keypad or via the BAS clear alarm command.
If active via trigger condition 1:
When the alarm occurs due to this trigger, it can auto reset the first two times each day, with the third occurrence
being manual reset.
For the auto reset occurrences, the alarm will reset automatically when the evaporator state is Run again. This
means the alarm stays active while the unit waits for flow, then it goes through the recirculation process after flow is
detected. Once the recirculation is complete, the evaporator goes to the Run state which will clear the alarm. After
three occurrences, the count of occurrences is reset and the cycle starts over if the manual reset flow loss alarm is
cleared.
If active via trigger condition 2:
If the flow loss alarm has occurred due to this trigger, it is always a manual reset alarm.
10.1.3. Evaporator Water Freeze Protect
Trigger: Evaporator LWT drops below evaporator freeze protect set point and LWT sensor fault is not active OR
Freeze Temp less than the Evap Freeze set point – 0.6°C (1.1°F) and Freeze Temp sensor fault isn’t
active
Action Taken: Rapid stop all circuits
Reset: This alarm can be cleared manually via the keypad, but only if the alarm trigger conditions no longer exist.
10.1.1. Evaporator Water Temperatures Inverted in Cool Mode
Trigger: Evap EWT is lower than the Evap LWT of 1 deg C, at least for 30 seconds while one circuit is running
and EWT and LWT sensors fault are not active
Action Taken: Pumpdown stop on all circuits
Reset: This alarm can be cleared manually via the keypad.
10.1.2. Evaporator LWT Sensor Fault
Trigger: Sensor shorted or open
Action Taken: Normal stop all circuits
Reset: This alarm can be cleared manually via the keypad or BAS command, but only if the sensor is back in range.
10.1.1. Freeze Temp Sensor Fault
Trigger: Sensor shorted or open
Action Taken: Normal stop of all circuits.
Reset: This alarm can be cleared manually via the keypad or via BAS command if the sensor is back in range.