Daikin Microtech III [21/44] The maximum unit capacity can be limited by a 4 to 20 ma signal on the demand limit analog input this function is only enabled if the demand limit option set point is set to enable the maximum unit capacity stage is determined as shown in the following tables two compressors

Daikin Microtech III [21/44] The maximum unit capacity can be limited by a 4 to 20 ma signal on the demand limit analog input this function is only enabled if the demand limit option set point is set to enable the maximum unit capacity stage is determined as shown in the following tables two compressors
- 21 -
8.7. Unit Capacity Overrides
Unit capacity limits can be used to limit total unit capacity in Cool mode only. Multiple limits may be active at any
time, and the lowest limit is always used in the unit capacity control.
8.7.1. Demand Limit
The maximum unit capacity can be limited by a 4 to 20 mA signal on the Demand Limit analog input. This function
is only enabled if the Demand Limit Option set point is set to ENABLE. The maximum unit capacity stage is
determined as shown in the following tables:
Two compressors:
Demand Limit Signal (%) Demand Limit (mA) Stage Limit
Demand Limit 50% Demand Limit 12 mA 1
Demand Limit < 50% Demand Limit < 12 mA None
Three compressors:
Demand Limit Signal (%) Demand Limit (mA) Stage Limit
Demand Limit 66.6% Demand Limit 14.6 mA 1
66.6% > Demand Limit 33.3% 14.6 mA > Demand Limit 9.3 mA 2
Demand Limit < 33.3% Demand Limit < 9.3 mA None
Four compressors:
Demand Limit Signal (%) Demand Limit (mA) Stage Limit
Demand Limit 75% Limit 16 mA 1
75% > Demand Limit 50% 16 mA > Limit 12 mA 2
50% > Demand Limit 25% 12 mA > Limit 8 mA 3
Demand Limit < 25% Demand Limit < 8 mA None
Six compressors:
Demand Limit Signal (%) Demand Limit (mA) Stage Limit
Demand Limit 83.3% Demand Limit 17.3 mA 1
83.3% > Demand Limit 66.7% 17.3 mA > Demand Limit 14.7 mA 2
66.7% > Demand Limit 50% 14.7 mA > Demand Limit 12mA 3
50% > Demand Limit 33.3% 12 mA > Demand Limit 9.3 mA 4
33.3% > Demand Limit 16.7% 9.3 mA > Demand Limit 6.7 mA 5
Demand Limit <16.7% Demand Limit <6.7 mA None
8.7.2. Network Limit
The maximum unit capacity can be limited by a network signal. This function is only enabled if the control source
is set to network and the Network Limit Option set point is set to ENABLE The maximum unit capacity stage is
based on the network limit value received from the BAS, and is determined as shown in the following tables:
Two compressors:
Network Limit Stage Limit
Network Limit 100% None
Network Limit < 50% 1
Three compressors:
Network Limit Stage Limit
Network Limit 100% None
66.6% > Network Limit 33.3% 2
Network Limit < 33.3% 1

Содержание